Fault
Fault type
code
Keypad
PCE
communication
fault
Parameters
DNE
downloading fault
Electronic
LL
underload fault
8.5.2 Other states
Fault
Fault type
code
PoFF
System power off
8.6 Common fault analysis
8.6.1 The motor does not work
Fault Tracking
Possible cause
The connection of the keypad wires
is not good or broken
The keypad wire is too long and
affected by strong interference
There is circuit fault on the
communication of the keypad and
main board
The connection of the keypad wire is
not good or broken
The keypad wire is too long and
affected by strong interference
There is a mistake on the data
storage of the keypad
The inverter will report the underload
pre-alarm according to the set value
Possible cause
System power off or the bus voltage
is too low
What to do
Check the keypad wire and ensure
whether there is mistake
Check the environment and avoid
the interference source
Change the hardware
Check the keypad wire and ensure
whether there is mistake
Change the hardware
Repack-up the data in the keypad
Check the load and the underload
pre-alarm point
What to do
Check the grid
99 - 144