Salicru CV50-008-4F User Manual page 82

Cv50 series
Table of Contents

Advertisement

Function
Name
code
the current stage
of the multi-step
speed
P17.35 AC input current
P17.36
Output torque
Motor overload
P17.37
counting
P17.38
PID output
Wrong download
P17.39
of parameters
Water supply
P24.00
selection
Press feedback
P24.01
source
Hibernation
P24.02
check
Starting
P24.03
frequency of the
hibernation
Starting
P24.04
pressure of
hibernation
Hibernation
P24.05
delay time
Hibernation
P24.06
awake
Awake
P24.07
frequency
Setting value of
P24.08
hibernation
awake
Minimum
P24.09
hibernation time
Valid auxiliary
P24.10
motor
82 - 144
Detailed instruction of parameters
speed
Range: 0~15
Display the input current in AC side.
Range: 0.0~5000.0 A
Display the output torque. Positive value is in the electromotion
state, and negative is in the power generating state.
Range : -3000.0Nm~3000.0 Nm
0~100 (100 is OL1 fault)
Display PID output
-100.00~100.00 %
0.00~99.99
P24 Group Water supply
0: Disabled
1: Enabled
0: AI1 setting value. Inverters ≤15 kW can be set by the
digital potentiometer on the keypad and AI1 setting is not
available for the devices ≥ 18.5 kW
1: AI2 setting value
2: AI3 setting value
3: HDI setting value
0: Hibernate as the setting frequency﹤P24.03
1: Hibernate as the feedback pressure﹥P24.04
0.00~P0.03 (the Max. frequency)
0.00~100.0 %
0.0~3600.0 s
0: Awake as the setting frequency﹥P24.07
1: Awake as the feedback pressure﹤P24.08
0.00~P0.03 (the Max. frequency)
0.00~100.0 %
0.0~3600.0 s
P24.10~P24.12 can make three motors to form a simple
Default
Modify
value
0.0 A
0.0 Nm
0
0.00 %
0.00
0
0
0
10.00 Hz
50.0 %
5.0 s
0
20.00 Hz
10.0 %
5.0 s
0
Function Parameters