8.6.2 Motor vibration
8.6.3 Overvoltage
Check the load and
adjust
100 - 144
OV fault
Check if the voltage range is in
the standard one or not ?
Yes
Check If UVW is short
circuited to to the earth and
the configuration of the output
side is right or not?
Yes
Check if the ACC/DEC
time is too short
No
Check if the load
Yes
motor is in abnormal
reverse running
No
If the it is the inverter
fault, please contact with
the company
No
Ensure the power supply
meets the need
Yes
Settle the short circuit
and confabulate rightly
Yes
Yes
Check if the ACC/DEC
time can be shortened
No
Check if it
Yes
needs to use
the options
No
Adjust the braking
options and the resistor
Shorten the ACC/DEC
time
Add braking optionds
Fault Tracking