Salicru CV50-008-4F User Manual page 74

Cv50 series
Table of Contents

Advertisement

Function
Name
code
of stage 4
Multi-step
P10.12
speed 5
Running time
P10.13
of stage 5
Multi-step
P10.14
speed 6
Running time
P10.15
of stage 6
Multi-step
P10.16
speed 7
Running time
P10.17
of stage 7
Multi-step
P10.18
speed 8
Running time
P10.19
of stage 8
Multi-step
P10.20
speed 9
Running time
P10.21
of stage 9
Multi-step
P10.22
speed 10
Running time
P10.23
of stage 10
Multi-step
P10.24
speed 11
Running time
P10.25
of stage 11
Multi-step
P10.26
speed 12
Running time
P10.27
of stage 12
Multi-step
P10.28
speed 13
Running time
P10.29
of stage 13
Multi-step
P10.30
speed 14
Running time
P10.31
of stage 14
Multi-step
P10.32
speed 15
Running time
P10.33
of stage 15
74 - 144
Detailed instruction of parameters
When S1=S2=S3=S4=OFF, the frequency input manner is
selected via code P00.06 or P00.07. When all S1=S2=S3=S4
terminals aren't off, it runs at multi-step which takes
precedence of keypad, analog value, high-speed pulse, PLC,
communication frequency input. Select at most 16 stages of
speed via the combination code of S1, S2, S3, and S4.
The start-up and stopping of multi-step running is determined
by function code P00.06, the relationship between
S1,S2,S3,S4 terminals and multi-step speed is as following:
S1 OFF ON OFF ON OFF ON OFF ON
S2 OFF OFF ON ON OFF OFF ON ON
S3 OFF OFF OFF OFF ON ON ON ON
S4 OFF OFF OFF OFF OFF OFF OFF OFF
Step 0
1
S1 OFF ON OFF ON OFF ON OFF ON
S2 OFF OFF ON ON OFF OFF ON ON
S3 OFF OFF OFF OFF ON ON ON ON
S4 ON ON ON ON ON ON ON ON
Step 8
9
Setting range of P10.(2n,1<n<17): -100.0~100.0 %
Setting range of P10.(2n+1,1<n<17): 0.0~6553.5 s (min)
2
3
4
5
6
10
11
12
13
14
Default
value
0.0 %
0.0 s
0.0 %
0.0 s
0.0 %
0.0 s
0.0 %
0.0 s
0.0 %
0.0 s
0.0 %
0.0 s
7
0.0 %
0.0 s
0.0 %
15
0.0 s
0.0 %
0.0 s
0.0 %
0.0 s
0.0 %
0.0 s
Function Parameters