Salicru CV50-008-4F User Manual page 45

Cv50 series
Table of Contents

Advertisement

Function
Name
code
Torque setting
P03.11
method
Keypad setting
P03.12
torque
Torque
P03.13
reference filter
time
Setting source
of forward
rotation
P03.14
upper-limit
frequency in
torque control
Setting source
of reverse
rotation
P03.15
upper-limit
frequency in
torque control
Torque control
forward rotation
upper-limit
P03.16
frequency
keypad defined
value
Torque control
reverse rotation
upper-limit
P03.17
frequency
keypad defined
value
Function Parameters
Detailed instruction of parameters
This parameter is used to enable the torque control mode,
and set the torque.
0: Torque control is invalid
1: Keypad setting torque(P03.12)
2: Analog AI1 setting torque. Inverters≤15kW can be set
by the digital potentiometer on the keypad and AI1 setting is
not available for the devices ≥18.5kW.
3: Analog AI2 setting torque
4: Analog AI3 setting torque
5: Pulse frequency HDI setting torque
6: Multi-step torque setting
7: MODBUS communication setting torque
8~10: Reserved
Note: Setting modes 2~10, 100% corresponds to three
times of the rated current of the motor.
Setting range: -300.0%~300.0% (rated current of the motor)
0.000~10.000s
0: Keypad
(P03.16 sets P03.14, P03.17 sets P03.15)
1: AI1. Inverters≤15kW can be set by the digital
potentiometer on the keypad and AI1 setting is not available
for the devices ≥ 18.5kW
2: AI2
3: AI3
4: Pulse frequency HDI setting upper-limit frequency
5: Multi-step setting upper-limit frequency
6: MODBUS communication setting upper-limit frequency
7~ 9: Reserved
Note: Setting method 1~9, 100% corresponds to the
maximum frequency
This function is used to set the upper limit of the frequency.
P03.16 sets the value of P03.14; P03.17 sets the value of
P03.15.
Setting range: 0.00 Hz~P00.03 (the Max. output frequency)
Default
Modify
value
0
50.0 %
0.010 s
0
0
50.00 Hz
50.00 Hz
45 - 144