Function
Name
code
Torque setting
P03.11
method
Keypad setting
P03.12
torque
Torque
P03.13
reference filter
time
Setting source
of forward
rotation
P03.14
upper-limit
frequency in
torque control
Setting source
of reverse
rotation
P03.15
upper-limit
frequency in
torque control
Torque control
forward rotation
upper-limit
P03.16
frequency
keypad defined
value
Torque control
reverse rotation
upper-limit
P03.17
frequency
keypad defined
value
Function Parameters
Detailed instruction of parameters
This parameter is used to enable the torque control mode,
and set the torque.
0: Torque control is invalid
1: Keypad setting torque(P03.12)
2: Analog AI1 setting torque. Inverters≤15kW can be set
by the digital potentiometer on the keypad and AI1 setting is
not available for the devices ≥18.5kW.
3: Analog AI2 setting torque
4: Analog AI3 setting torque
5: Pulse frequency HDI setting torque
6: Multi-step torque setting
7: MODBUS communication setting torque
8~10: Reserved
Note: Setting modes 2~10, 100% corresponds to three
times of the rated current of the motor.
Setting range: -300.0%~300.0% (rated current of the motor)
0.000~10.000s
0: Keypad
(P03.16 sets P03.14, P03.17 sets P03.15)
1: AI1. Inverters≤15kW can be set by the digital
potentiometer on the keypad and AI1 setting is not available
for the devices ≥ 18.5kW
2: AI2
3: AI3
4: Pulse frequency HDI setting upper-limit frequency
5: Multi-step setting upper-limit frequency
6: MODBUS communication setting upper-limit frequency
7~ 9: Reserved
Note: Setting method 1~9, 100% corresponds to the
maximum frequency
This function is used to set the upper limit of the frequency.
P03.16 sets the value of P03.14; P03.17 sets the value of
P03.15.
Setting range: 0.00 Hz~P00.03 (the Max. output frequency)
Default
Modify
value
0
○
50.0 %
○
0.010 s
○
0
○
0
○
50.00 Hz
○
50.00 Hz
○