Function
Name
code
P14.01
Baud Rate
Digital bit
P14.02
checkout setting
Communica tion
P14.03
answer delay
Function Parameters
Detailed instruction of parameters
point communication between the upper monitor and the drive.
Note: The address of the slave cannot set to 0.
Set the digital transmission speed between the upper
monitor and the inverter.
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
6: 57600BPS
7: 115200BPS
Note: The baud rate between the upper monitor and the
inverter must be the same. Otherwise, the communication
is not applied. The bigger the baud rate, the quicker the
communication speed.
The data format between the upper monitor and the inverter
must be the same. Otherwise, the communication is not
applied.
0: No check (N,8,1) for RTU
1: Even check (E,8,1) for RTU
2: Odd check (O,8,1) for RTU
3: No check (N,8,2) for RTU
4: Even check (E,8,2) for RTU
5: Odd check (O,8,2) for RTU
6: No check (N,7,1) for ASCII
7: Even check (E,7,1) for ASCII
8: Odd check (O,7,1) for ASCII
9: No check (N,7,2) for ASCII
10: Even check (E,7,2) for ASCII
11: Odd check (O,7,2) for ASCII
12: No check (N,8,1) for ASCII
13: Even check (E,8,1) for ASCII
14: Odd check (O,8,1) for ASCII
15: No check (N,8,2) for ASCII
16: Even check (E,8,2) for ASCII
17: Odd check (O,8,2) for ASCII
0~200 ms
It means the interval time between the interval time when
the drive receive the data and send it to the upper monitor.
If the answer delay is shorter than the system processing
time, then the answer delay time is the system processing
time. If the answer delay is longer than the system
processing time, then after the system deal with the data,
waits until achieving the answer delay time to send the data
to the upper monitor.
Default
Modify
value
4
1
5
79 - 144