Terminal
name
PE
Grounding terminal
Provide the input switch working power supply from external to internal.
PW
Voltage range: 12~24V
The inverter provides the power supply for users with a maximum output current of 200mA
24V
COM
+24V common terminal
S1
Switch input 1
S2
Switch input 2
S3
Switch input 3
S4
Switch input 4
S5
Switch input 5
S6
Switch input 6
S7
Switch input 7
S8
Switch input 8
This terminal can be used as high frequency input channel.
HDI
Max. input frequency: 50kHz
1. Switch output: 200mA/30V
HDO
2. Output frequency range: 0~50kHz
COM
+24V common terminal
CME
Common terminal of HDO and Y1, short-connected with COM in factory
1.Switch capability: 200mA/30V
Y1
2.Output frequency range: 0~1kHz
RS485 communication interface and RS485 differential signal interface
485+
If it is the standard RS485 communication interface, please use twisted pairs or shielded
485-
cable.
4.3.6 Input /Output signal connection figure
Please use U-shaped contact tag to set NPN mode or PNP mode and the internal or external power supply.
The default setting is NPN internal mode.
If the signal is from NPN transistor, please set the U-shaped contact tag between +24V and PW as below
according to the used power supply.
Installation Guidelines
Description
1. Internal impedance: 3.3kΩ
2. 12~30V voltage input is available
3. The terminal is the dual-direction input terminal supporting both
NPN and PNP
4. Max input frequency: 1kHz
5. All are programmable digital input terminal. User can set the
terminal function through function codes.
Fig 4-21 U-shaped contact tag