Fault Diagnosis And Countermeasures - Salicru ControlVIT CV10 series Quick Start Manual

Advertisement

P07 Group Human-Machine Interface
Current fault
0: No fault
P07.27
type
4: OC1
5: OC2
Previous fault
P07.28
6: OC3
type
7: OV1
Previous 2
P07.29
8: OV2
fault type
9: OV3
Previous 3
10: UV
P07.30
fault type
11: Motor overload (OL1)
Previous 4
12: The inverter overload (OL2)
P07.31
fault type
15: Overheat of the rectifier module (OH1)
16: Overheat fault of the inverter module (OH2)
17: External fault (EF)
18: 485 communication fault (CE)
21: EEPROM operation fault (EEP)
Previous 5
P07.32
22: PID response offline fault (PIDE)
fault type
24: Running time arrival (END)
25: Electrical overload (OL3)
36: Undervoltage fault (LL)
Current fault
P07.33
running
frequency
Ramp
reference
P07.34
frequency at
current fault
Output voltage
P07.35
at current fault
Output current
P07.36
at current fault
Bus voltage at
P07.37
current fault
Max.
P07.38
temperature at
current fault
Input terminal
P07.39
state at
current fault
Output
P07.40
terminal state
at current fault
P08 Group Enhanced function
Time of fault
P08.28
reset
Setting range of P08.28:0~10
Interval time of
Setting range of P08.29:0.1~3600.0s
P08.29
automatic fault
reset
Energy
0:Disabled
P08.37
Braking
1:Enabled
enable
P11 Group
Sudden power
loss frequency
0: Enabled
P11.01
decreasing
1: Disabled
function
selection
Frequency
decreasing
Setting range: 0.00Hz/s~P00.03 (the Max. frequency)
P11.02
ratio of sudden
Frequency-decreasing point of sudden power loss: 260V
power loss
Overvoltage
0:Disabled
P11.03
speed loss
1:Enabled
protection
Overvoltage
speed loss
P11.04
120~150%
voltage
protection
Current limit
P11.05
action
selection
Setting range of P11.05:
Automatic
0:current limit invalid
P11.06
current limit
1:current limit valid
level
Setting range of P11.06:50.0~200.0%
The
Setting range of P11.07:0.00~50.00Hz/s
decreasing
P11.07
ratio during
current limit
Overload
Setting range of P11.08: 0x000~0x131
pre-alarm of
LED ones:
P11.08
the motor or
0: Overload pre-alarm of the motor, comply with the rated
the inverter
current of the motor
1: Overload pre-alarm of the inverter, comply with the
Overload
rated current of the inverter
P11.09
pre-alarm test
LED tens:
level
0: The inverter continues to work after underload pre-alarm
1: The inverter continues to work after underload pre-alarm
and the inverter stops to run after overload fault
2: The inverter continues to work after overload pre-alarm
and the inverter stops to run after underload fault
Overload
3: The inverter stops when overloading or underloading.
P11.10
pre-alarm
LED hundreds:
detection time
0: Detection all the time
1: Detection in constant running
Setting range of P11.09: P11.11~200%
Setting range of P11.10: 0.1~60.0s
Detection level
of the
P11.11
underload
pre-alarm
Setting range of P11.11: 0~P11.09
Setting range of P11.12: 0.1~60.0s
Detection time
of the
P11.12
underload
pre-alarm
0x00~0x11
LED ones:
Output
0: Action under fault undervoltage
terminal action
P11.13
1: No action under fault undervoltage
selection
LED tens:
during fault
0: Action during the automatic reset
1: No action during the automatic reset
●5.5 Start up (press RUN/TUNE)
 
0.00Hz
0.00Hz
0V
0.0A
0.0V
0.0℃
0
0
0
1.0s
0
Protective parameters
0
10.00Hz/s
1
120%
1
160.0%
10.00Hz/s
0x000
150%
1.0s
50%
1.0s
0x00
Quick Start Guide of CV10- ControlVIT Series
●5.6 Stop (press STOP/RST)
Ensure the motor runs at right direction and there is no fault.
Diagram of quick start-up
 
 
 
 

Fault diagnosis and countermeasures

 
Do as the following after the inverter fault:
1. Check to ensure there is nothing wrong with the keypad. If not, please contact with SALICRU.
2. If there is nothing wrong, please check P07 and ensure the corresponding recorded fault parameters
to confirm the real state when the current fault occurs by all parameters.
 
3. See the following table for detailed solution and check the corresponding abnormal state.
4. Eliminate the fault and ask for relative help.
 
5. Check to eliminate the fault and carry out fault reset to run the inverter.
Fault code
Fault type
Over-current when
OC1
acceleration
 
Over-current when
OC2
deceleration
Over-current when
OC3
constant speed
 
running
 
Over-voltage when
OV1
acceleration
Over-voltage when
OV2
deceleration
 
Over-voltage when
OV3
constant speed
running
4 / 5
Possible cause
Solutions
1. The acceleration or
1. Increase the ACC time
deceleration is too fast.
2. Check the input power
2. The voltage of the grid is
3. Select the inverter with a
too low.
larger power
3. The power of the inverter is
4. Check if the load is short
too low.
circuited (the grounding short
4. The load transients or
circuited or the wire short
rotation is abnormal.
circuited) or the rotation is not
5. The grounding is short
smooth.
circuited or the output is
5. Check the output
phase loss.
configuration.
6. There is strong external
6. Check if there is strong
interference.
interference.
7. The overvoltage stall
7. Check the setting of relative
protection is not opened.
function codes.
1. Check the input power
2. Check if the DEC time of the
1. The input voltage is
load is too short or the inverter
abnormal.
starts during the rotation of the
2. There is large energy
motor or it needs to add the
feedback.
dynamic braking components.
3. No braking components.
3. Install the braking
4. Dynamic braking energy
components.
unit is not activated
4. Check the setting of relative
function codes.
EL086A01