The Definition Of Data Address - Salicru CV50-008-4F User Manual

Cv50 series
Table of Contents

Advertisement

ASCII master command message (the command
sent by the master to the inverter)
START
ADDR
CMD
High bit of starting address
Low bit of starting address
High bit of data number
Low bit of data number
Byte number
High bit of data 0004H content
Low bit of data 0004H content
High bit of data 0005H content
Low bit of data 0005H content
LRC CHK Hi
LRC CHK Lo
END Hi
END Lo

9.5 The definition of data address

The address definition of the communication data in this part is to control the running of the inverter and get
the state information and relative function parameters of the inverter.
9.5.1 The rules of parameter address of the function codes
The parameter address occupies 2 bytes with the fact that the high bit is in the front and the low bit is in the
behind. The range of high and low byte are: high byte—00~ffH; low byte—00~ffH. The high byte is the group
number before the radix point of the function code and the low byte is the number after the radix point. But
both the high byte and the low byte should be changed into hex. For example P05.06, the group number
before the radix point of the function code is 05, then the high bit of the parameter is 05, the number after the
radix point 06, then the low bit of the parameter is 06, then the function code address is 0506H and the
parameter address of P10.01 is 0A01H.
116 - 144
ASCII slave response message (the message
sent by the inverter to the master)
':'
'0'
'2'
'1'
'0'
'0'
High bit of starting address
'0'
'0'
Low bit of starting address
'4'
'0'
High bit of data number
'0'
'0'
Low bit of data number
'2'
'0'
'4'
'1'
'3'
'8'
'8'
'0'
'0'
'3'
'2'
'1'
'7'
CR
LF
START
ADDR
CMD
LRC CHK Hi
LRC CHK Lo
END Hi
END Lo
Communication Protocol
':'
'0'
'2'
'1'
'0'
'0'
'0'
'0'
'4'
'0'
'0'
'0'
'2'
'E'
'8'
CR
LF