Fault
Fault type
code
Over-current when
OC3
constant speed
running
Over-voltage
OV1
when acceleration
Over-voltage
OV2
when deceleration
Over-voltage
OV3
when constant
speed running
DC bus
UV
Under-voltage
OL1
Motor overload
OL2
Inverter overload
OL3
Electrical overload
SPI
Input phase loss
SPO
Output phase loss
OH1
Rectify overheat
OH2
IGBT overheat
EF
External fault
Fault Tracking
Possible cause
The load transients or rotation is
abnormal
The grounding is short circuited or
the output is phase loss
There is strong external interference
The overvoltage stall protection is
not opened
The input voltage is abnormal
There is large energy feedback
No braking components
Braking energy is not evacuated
The voltage of the power supply is
too low
The overvoltage stall protection is
not opened
The voltage of the power supply is
too low
The motor setting rated current is
incorrect
The motor stall or load transients are
too strong
The acceleration is too fast
Reset the rotating motor
The voltage of the power supply is
too low
The load is too heavy
The motor power is too small
The inverter will report overload
pre-alarm according to the set value
Phase loss or fluctuation of input
R,S,T
U,V,W phase loss (or serious
asymmetrical three phase of the load)
Air duct jam or fan damage
Ambient temperature is too high
The time of overload running is too
long
S1...S8 external fault input terminals
action
What to do
Check if the load is short circuited
(the grounding short circuited or the
wire short circuited) or the rotation is
not smooth
Check the output configuration.
Check if there is strong interference
Check the setting of relative function
codes
Check the input power
Check if the DEC time of the load is
too short or the inverter starts during
the rotation of the motor or it needs
to add the dynamic bracking
components
Install the braking components
Check the setting of relative function
codes
Check the input power of the supply
line
Check the setting of relative function
codes
Check the power of the supply line
Reset the rated current of the motor
Check the load and adjust the torque
lift
Increase the ACC time
Avoid the restarting after stopping
Check the power of the supply line
Select an inverter with bigger power
Select a proper motor
Check the load and the overload
pre-alarm point.
Check input power
Check installation distribution
Check the output distribution
Check the motor and cable
Clean the air duct or the fan
Reduce the ambient temperature
Check the external device input
97 - 144