Function
Name
code
Detection level
P11.11
of the underload
pre-alarm
Detection time of
P11.12
the underload
pre-alarm
Output terminal
P11.13
action selection
during fault
Extension
P11.16
functions
selection
P13 Group Control parameters of Short circuit braking
Braking current
P13.13
of short-circuit
Braking
retention time of
P13.14
starting short
circuit
Braking
retention time of
P13.15
stopping short
circuit
Local
P14.00
communication
address
78 - 144
Detailed instruction of parameters
Setting range of P11.09: P11.11~200 %
Setting range of P11.10: 0.1~3600.0 s
If the inverter current or the output current is lower than
P11.11, and its lasting time is beyond P11.12, the inverter
will output underload pre-alarm.
Setting range of P11.11: 0~P11.09
Setting range of P11.12: 0.1~3600.0 s
Select the action of fault output terminals on undervoltage
and fault reset.
0x00~0x11
LED ones:
0: Action under fault undervoltage
1: No action under fault undervoltage
LED tens:
0: Action during the automatic reset
1: No action during the automatic reset
0x00~0x11
LED ones: Voltage drop frequency-decreasing selection
0: Voltage drop frequency-decreasing selection disabled
1: Voltage drop frequency-decreasing selection enabled
LED tens: Step 2 ACC/DEC time option
0: Step 2 ACC/DEC time option disabled
1: Step 2 ACC/DEC time option enable,when running
frequency more than P08.36, ACC/DEC time switch to step
2 ACC/DEC time
When P01.00=0 during the starting of the inverter, set
P13.14 to a non-zero value to enter the short circuit braking.
When the running frequency is lower than P01.09 during
the stopping of the inverter, set 13.15 to a non-zero value to
enter into stopping short circuited braking and then carry
out the DC braking at the time set by P01.12 (refer to the
instruction of P01.09~P01.12) .
Setting range of P13.13: 0.0~150.0% (the inverter)
Setting range of P13.14: 0.00~50.00s
Setting range of P13.15: 0.00~50.00s
P14 Group Serial communication
The setting range: 1~247
When the master is writing the frame, the communication
address of the slave is set to 0; the broadcast address is the
communication address. All slaves on the MODBUS fieldbus
can receive the frame, but the slave doesn't answer.
The communication address of the drive is unique in the
communication net. This is the fundamental for the point to
Default
Modify
value
50 %
1.0 s
0x00
00
0.0 %
0.00 s
0.00 s
1
Function Parameters