Function
Name
code
Simple PLC 0~7
P10.34
stage ACC/DEC
time selection
Simple PLC
8~15 stage
P10.35
ACC/DEC time
selection
PLC restart
P10.36
mode
Multi-step time
P10.37
unit selection
Phase loss
P11.00
protection
Function Parameters
Detailed instruction of parameters
Below is the detailed instruction:
Function
Binary bit
code
BIT1
BIT0
BIT3
BIT2
BIT5
BIT4
BIT7
BIT6
P10.34
BIT9
BIT8
BIT11 BIT10
BIT13 BIT12
BIT15 BIT14
BIT1
BIT0
BIT3
BIT2
BIT5
BIT4
BIT7
BIT6
P10.35
BIT9
BIT8
BIT11 BIT10
BIT13 BIT12
BIT15 BIT14
After the users select the corresponding ACC/DEC time,
the combined 16 binary bits will change into decimal bit,
and then set the corresponding function codes.
Setting range: 0x0000~0xFFFF
0: Restart from the first stage. Stop during running (cause by
the stop command, fault or power loss), run from the first stage
after restart.
1: Continue to run from the stop frequency; stop during
running (cause by stop command or fault), the inverter will
record the running time automatically, enter into the stage after
restart and keep the remaining running at the setting frequency.
0: Seconds; the running time of all stages is counted by second
1: Minutes; the running time of all stages is counted by minutes
P11 Group Protective parameters
0x000~0x111
LED ones:
0: Input phase loss software protection disable
1: Input phase loss software protection enable
LED tens:
0: Output phase loss protection disable
1: Output phase loss protection enable
LED hundreds:
0: Input phase loss hardware protection disable
1: Input phase loss hardware protection enable
ACC/
ACC/
ACC/
Step
DEC
DEC
DEC
0
1
2
0
00
01
10
1
00
01
10
2
00
01
10
3
00
01
10
4
00
01
10
5
00
01
10
6
00
01
10
7
00
01
10
8
00
01
10
9
00
01
10
10
00
01
10
11
00
01
10
12
00
01
10
13
00
01
10
14
00
01
10
15
00
01
10
Default
Modify
value
0x0000
ACC/
DEC
3
11
11
11
11
11
11
11
11
11
0x0000
11
11
11
11
11
11
11
0
0
111
75 - 144