the password (set P07.00 to any non-zero number), the system will come into the state of password
verification firstly after the user press PRG/ESC to come into the function code editing state. And then
"0.0.0.0.0." will be displayed. Unless the user input right password, they cannot enter into the system. For the
factory setting parameter zone, it needs correct factory password (remind that the users can not modify the
factory parameters by themselves, otherwise, if the parameter setting is incorrect, damage to the inverter may
occur). If the password protection is unlocked, the user can modify the password freely and the inverter will
work as the last setting one. When P07.00 is set to 0, the password can be canceled. If P07.00 is not 0 during
powering on, then the parameter is protected by the password. When modify the parameters by serial
communication, the function of the password follows the above rules too.
Function
Name
code
Speed control
P00.00
mode
Run command
P00.01
channel
Communication
P00.02
selection
Function Parameters
Detailed instruction of parameters
P00 Group Basic function group
1: Sensorless vector control mode 1 (applying to
asynchronous motors))
No need to install encoders. It is suitable in cases with high
speed control accuracy for accurate speed and torque
control at all power ratings.
2: SVPWM control (V/F control)
No need to install encoders. It can improve the control
accuracy with the advantages of stable operation, valid
low-frequency torque boost and current vibration
suppression and the functions of slip compensation and
voltage adjustment.
Select the run command channel of the inverter.
The control command of the inverter includes: start-up,
stop, forward, reverse, jogging and fault reset.
0: Keypad running command channel ("LOCAL/REMOT"
light off)
Carry out the command control by RUN, STOP/RST on the
keypad.
Set the multi-function key QUICK/JOG as FWD/REV
shifting function (P07.02=3) to change the running direction;
press RUN and STOP/RST simultaneously in running state
to make the inverter coast to stop.
1: Terminal running command channel
("LOCAL/REMOT" flickering)
Carry out the running command control by the forward
rotation, reverse rotation and forward jogging and reverse
jogging of the multi-function terminals
2: Communication running command channel
("LOCAL/REMOT" on)
The running command is controlled by the upper monitor
via communication.
0: MODBUS communication
1~3: Reserved
Default
Modify
value
2
0
0