Salicru CV50-008-4F User Manual page 50

Cv50 series
Table of Contents

Advertisement

Function
Name
code
Maximum
P04.31
output voltage
Minimum
P04.32
output voltage
Weaking
coefficient at
P04.33
constant power
zone
HDI input
P05.00
selection
S1 terminal
P05.01
function
selection
S2 terminal
P05.02
function
selection
S3 terminal
P05.03
function
selection
S4 terminal
P05.04
function
selection
S5 terminal
P05.05
function
selection
S6 terminal
P05.06
function
selection
50 - 144
Detailed instruction of parameters
Set the upper and low limit of the output voltage.
The setting range of P04.31: P04.32~100.0%
(the rated voltage of the motor)
The setting range of P04.32: 0.0%~ P04.31
(the rated voltage of the motor)
Used to adjust the output voltage of inverter in SVPWM
mode when weaking magnetic.
Note: Invalid in constant-torque mode.
The setting range of P04.33: 1.00~1.30
P05 Group Input terminals
0: HDI is high pulse input. See P05.49~P05.54
1: HDI is switch input
0: No function
1: Forward rotation
2: Reverse rotation
3: 3-wire control
4: Forward jogging
5: Reverse jogging
6: Coast to stop
7: Fault reset
8: Operation pause
9: External fault input
10: Increasing frequency setting (UP)
11: Decreasing frequency setting (DOWN)
12: Cancel the frequency change setting
13: Shift between A setting and B setting
14: Shift between combination setting and A setting
15: Shift between combination setting and B setting
16: Multi-step speed terminal 1
17: Multi-step speed terminal 2
Default
Modify
value
100.0 %
0.0 %
1.00
0
1
4
7
0
0
0
Function Parameters