Salicru CV50-008-4F User Manual page 69

Cv50 series
Table of Contents

Advertisement

Function
Name
code
Integral ratio of
P08.43
the keypad
potentiometer
UP/DOWN
P08.44
terminals
control setting
UP terminal
P08.45
frequency
changing ratio
DOWN terminal
P08.46
frequency
changing ratio
Action selection
for frequency
P08.47
settings on
power off
High bit of initial
P08.48
power
consumption
Low bit of initial
P08.49
power
consumption
Magnetic flux
P08.50
braking
Function Parameters
Detailed instruction of parameters
2: Invalid for multi-step speed when multi-step speed has
the priority
LED hundreds: action selection during stopping
0: Setting is valid
1: Valid during running, cleared after stopping
2: Valid during running, cleared after receiving the stop command
LED thousands: ∧/∨ keys and digital potentiometer
integral function
0: The integral function is valid
1: The integral function is invalid
0.01~10.00s
0x00~0x221
LED ones: frequency control selection
0: UP/DOWN terminals setting valid
1: UP/DOWN terminals setting invalid
LED tens: frequency control selection
0: Only valid when P00.06=0 or P00.07=0
1: All frequency means are valid
2: When the multi-step are priority, it is invalid to the multi-step
LED hundreds: action selection when stop
0: Setting valid
1: Valid in the running, clear after stop
2: Valid in the running, clear after receiving the stop commands
0.01~50.00 Hz/s
0.01~50.00 Hz/s
0x000~0x111
LED ones: Action for digital adjustable frequency on power off
0: Save on power off
1: Clear on power off
LED tens: Action for MODBUS frequency setting on power off
0: Save on power off
1: Clear on power off
LED hundreds: Action for other-mode frequency setting on
power off
0: Save on power off
1: Clear on power off
This parameter is used to set the original value of the power
consumption.
The original value of the power consumption
=P08.48*1000+ P08.49
Setting range of P08.48: 0~59999 kWh (x1000)
Setting range of P08.49: 0.0~999.9 kWh
This function code is used to enable magnetic flux.
0: Invalid.
100~150: the bigger the coefficient, the stronger the
Default
Modify
value
0.10 s
0x000
0.50
Hz/s
0.50
Hz/s
0x000
0 kWh
0.0 kWh
0
69 - 144