Salicru CV50-008-4F User Manual page 80

Cv50 series
Table of Contents

Advertisement

Function
Name
code
Communica tion
P14.04
overtime fault
time
Transmission
P14.05
fault processing
Communication
P14.06
processing
action selection
P17.00
Sett frequency
Output
P17.01
frequency
Ramp reference
P17.02
frequency
P17.03
Output voltage
P17.04
Output current
P17.05
Motor speed
P17.08
Motor power
P17.09
Output torque
Motor frequency
P17.10
evaluation
P17.11
DC bus voltage Display current DC bus voltage of the inverter
80 - 144
Detailed instruction of parameters
0.0 (invalid), 0.1~60.0 s
When the function code is set as 0.0, the communication
overtime parameter is invalid.
When the function code is set as non-zero, if the interval
time between two communications exceeds the
communication overtime, the system will report "RS485
communication faults" (CE).
Generally, set it as invalid; set the parameter in the continuous
communication to monitor the communication state.
0: Alarm and stop freely
1: No alarm and continue to run
2: No alarm and stop according to the stop means (only
under the communication control)
3: No alarm and stop according to the stop means (under
all control modes)
0x00~0x11
LED ones:
0: Operation with response. The drive will respond to all
reading and writing commands of the upper monitor.
1: Operation without response. The drive only responds to the
reading command other than the writing command of the drive.
The communication efficiency can be increased by this method.
LED tens:
0: Communication encrypting valid
1: Communication encrypting invalid
P17 Group Monitoring function
Display current set frequency of the inverter
Range: 0.00Hz~P00.03
Display current output frequency of the inverter
Range: 0.00Hz~P00.03
Display current ramp reference frequency of the inverter
Range: 0.00Hz~P00.03
Display current output voltage of the inverter
Range: 0~1200 V
Display current output current of the inverter
Range: 0.0~3000.0 A
Display the rotation speed of the motor.
Range: 0~65535 RPM
Display current motor power
Range:-300~300% (the rated current of the motor)
Display the current output torque of the inverter.
Range: -250.0~250.0 %
Evaluate the motor rotor frequency on open loop vector.
Range: 0.00Hz~ P00.03
Default
Modify
value
0.0 s
0
0x00
0.00 Hz
0.00 Hz
0.00 Hz
0 V
0.0 A
0 RPM
0.0 %
0.0 %
0.00 Hz
0.0 V