Function
Name
code
Setting counting
P08.25
value
Reference
P08.26
counting value
P08.27 Set running time
Fault Auto-reset
P08.28
attempts
Interval time of
P08.29
automatic fault
reset
Frequency
P08.30
decreasing ratio
in drop control
FDT1 electrical
P08.32
level detection
value
FDT1 retention
P08.33
detection value
66 - 144
Detailed instruction of parameters
The setting range of P08.16: 0.0~50.0% (relative to the
traverse range)
The setting range of P08.17: 0.1~3600.0s
The setting range of P08.18: 0.1~3600.0s
The counter works by the input pulse signals of the HDI
terminals.
When the counter achieves a fixed number, the
multi-function output terminals will output the signal of "fixed
counting number arrival" and the counter go on working;
when the counter achieves a setting number, the
multi-function output terminals will output the signal of
"setting counting number arrival", the counter will clear all
numbers and stop to recount before the next pulse.
The setting counting value P08.26 should be no more than
the setting counting value P08.25.
The function is illustrated as below:
Setting range of P08.25: P08.26~65535
Setting range of P08.26: 0~P08.25
Pre-set running time of the inverter. When the accumulative
running time achieves the set time, the multi-function digital
output terminals will output the signal of "running time arrival".
Setting range: 0~65535 min
Number of fault auto-reset attempts: set the fault reset
attempts by selecting this function. If the reset attempts
exceed this set value, the inverter will stop for the fault and
wait to be repaired.
The interval time of the fault reset: The interval between
the time when the fault occurs and the time when the reset
action occurs.
Setting range of P08.28: 0~10
Setting range of P08.29: 0.1~3600.0s
The output frequency of the inverter changes as the load.
And it is mainly used to balance the power when several
inverters drive one load.
Setting range: 0.00~10.00Hz
When the output frequency exceeds the corresponding
frequency of FDT electrical level, the multi-function digital
output terminals will output the signal of "frequency level
detect FDT" until the output frequency decreases to a value
lower than (FDT electrical level—FDT retention detection
Default
Modify
value
0
0
0 m
0
1.0 s
0.00 Hz
50.00 Hz
5.0 %
Function Parameters