Function
Name
code
Lower limit of
P06.17
AO1 output
Correspon ding
P06.18
AO1 output to
the lower limit
Upper limit of
P06.19
AO1 output
Correspon ding
P06.20
AO1 output to
the upper limit
AO1 output filter
P06.21
time
Lower limit of
P06.22
AO2 output
Correspon ding
P06.23
AO2 output to
the lower limit
Upper limit of
P06.24
AO2 output
Correspon ding
P06.25
AO2 output to
the upper limit
AO2 output filter
P06.26
time
Lower limit of
P06.27
HDO output
Correspon ding
P06.28
HDO output to
the lower limit
Upper limit of
P06.29
HDO output
Correspon ding
P06.30
HDO output to
the upper limit
HDO output filter
P06.31
time
58 - 144
Detailed instruction of parameters
not available for the devices ≥18.5kW
11: Analog AI2 input value
12: Analog AI3 input value
13: High speed pulse HDI input value
14: MODBUS communication set value 1
15: MODBUS communication set value 2
22: Torque current (corresponds to 3 times of the rated
current of the motor)
23: Ramp reference frequency (with sign)
These function codes define the relative relationship
between the output value and analog output. When the
output value exceeds the range of set maximum or
minimum output, it will count according to the low-limit or
upper-limit output.
When the analog output is current output, 1mA equals to
0.5V.
In different cases, the corresponding analog output of 100%
of the output value is different. Please refer to each
application for detailed information.
A
O
10V (20m A )
0.0%
Setting range of P06.18: 0.00V~10.00V
Setting range of P06.19: P06.17~100.0%
Setting range of P06.20: 0.00V~10.00V
Setting range of P06.21: 0.000s~10.000s
Setting range of P06.22: 0.0%~P06.24
Setting range of P06.23: 0.00V~10.00V
Setting range of P06.24: P06.22~100.0%
Setting range of P06.25: 0.00V~10.00V
Setting range of P06.26: 0.000s~10.000s
Setting range of P06.27: 0.000s~10.000s
Setting range of P06.28: 0.00~50.00kHz
Setting range of P06.29: P06.27~100.0%
Setting range of P06.30: 0.00~50.00kHz
Setting range of P06.31: 0.000s~10.000s
100.0%
Function Parameters
Default
Modify
value
0.0%
0.00V
100.0%
10.00V
0.000s
0.0%
0.00V
100.0%
10.00V
0.000s
0.00%
0.00kHz
100.0%
50.00
kHz
0.000s