Function
Name
code
S7 terminal
P05.07
function
selection
S8 terminal
P05.08
function
selection
HDI terminal
P05.09
function
selection
Polarity
P05.10
selection of the
input terminals
P05.11 Switch filter time
Virtual terminals
P05.12
setting
Function Parameters
Detailed instruction of parameters
18: Multi-step speed terminal 3
19: Multi- step speed terminal 4
20: Multi- step speed pause
21: ACC/DEC time option 1
22: ACC/DEC time option 2
23: Simple PLC stop reset
24: Simple PLC pause
25: PID control pause
26: Traverse Pause (stop at the current frequency)
27: Traverse reset (return to the center frequency)
28: Counter reset
29: Torque control prohibition
30: ACC/DEC prohibition
31: Counter trigger
32: Length reset
33: Cancel the frequency change setting temporarily
34: DC brake
36: Shift the command to the keypad
37: Shift the command to the terminals
38: Shift the command to the communication
39: Pre-exciting command
40: Clear the power
41: Keep the power
61: PID pole switching
The function code is used to set the polarity of the input
terminals.
Set the bit to 0: the input terminal is anode.
Set the bit to 1: the input terminal is cathode.
BIT0
BIT1
S1
S2
BIT5
BIT6
S6
S7
Setting range: 0x000~0x1FF
Set the sample filter time of S1~S8 and HDI terminals. If the
interference is strong, increase the parameter to avoid the
disoperation.
0.000~1.000s
0x000~0x1FF (0: Disabled, 1:Enabled )
BIT0: S1 virtual terminal
BIT1: S2 virtual terminal
BIT2: S3 virtual terminal
BIT3: S4 virtual terminal
BIT4: S5 virtual terminal
BIT5: S6 virtual terminal
BIT2
BIT3
BIT4
S3
S4
S5
BIT7
BIT8
S8
HDI
Default
Modify
value
0
0
0
0x000
0.010 s
0x000
51 - 144