Function
Name
code
Speed display
P03.27
selection of
vector control
Compensation
P03.28
coefficient of
static friction
Compensation
P03.29
coefficient of
dynamic friction
Motor 1 V/F
P04.00
curve setting
Function Parameters
Detailed instruction of parameters
0: Display the actual value
1: Display the setting value
0.0~100.0%
Adjust P03.28 to compensate the coefficient of static
friction.
0.0~100.0%
Adjust P03.29 to compensate the coefficient of static
friction.
P04 Group SVPWM control
These function codes define the V/F curve of CV50 motor 1,
and meet the need of different loads.
0: Straight line V/F curve, applying to the constant torque
load
1: Multi-dots V/F curve
th
2: 1.3
power low torque V/F curve
th
3: 1.7
power low torque V/F curve
th
4: 2.0
power low torque V/F curve
Curves 2~4 apply to the torque loads such as fans and
water pumps. Users can adjust according to the features of
the loads to achieve a best energy-saving effect.
5: Customized V/F (V/F separation). In this mode, V can
be separated from f and f can be adjusted through the
frequency reference channel set by P00.06 or the voltage
reference channel set by P04.27 to change the feature of
the curve.
Note: V
in the below picture is the motor rated voltage and
b
f
is the motor rated frequency.
b
Default
Modify
value
0
0.0 %
0.0 %
0
47 - 144