Salicru CV50-008-4F User Manual page 72

Cv50 series
Table of Contents

Advertisement

Function
Name
code
Output upper
P09.09
limit of PID
Output lower
P09.10
limit of PID
Feedback offline
P09.11
detection value
Feedback offline
P09.12
detection time
PID adjustment
P09.13
selection
72 - 144
Detailed instruction of parameters
Setting range: 0.0~100.0%
These parameters are used to set the upper and lower limit
of the PID adjustor output.
100.0 % corresponds to Max. frequency or the Max. voltage
of ( P04.31)
Setting range of P09.09: P09.10~100.0%
Setting range of P09.10: -100.0%~P09.09
Set the PID feedback offline detection value, when the
detection value is smaller than or equal to the feedback
offline detection value, and the lasting time exceeds the set
value in P09.12, the inverter will report "PID feedback offline
fault" and the keypad will display PIDE.
Setting range of P09.11: 0.0~100.0%
Setting range of P09.12: 0.0~3600.0s
0x0000~0x1111
LED ones:
0: Keep on integral adjustment when the frequency
achieves the upper and low limit; the integration shows the
change between the reference and the feedback unless it
reaches the internal integral limit. When the trend between
the reference and the feedback changes, it needs more
time to offset the impact of continuous working and the
integration will change with the trend.
1: Stop integral adjustment when the frequency reaches
the upper and low limit. If the integration keeps stable, and
the trend between the reference and the feedback changes,
the integration will change with the trend quickly.
LED tens (P00.08 is 0)
0: Same with the setting direction; if the output of PID
adjustment is different from the current running direction,
the internal control will output 0 forcedly.
1: Opposite to the setting direction
LED hundreds (P00.08 is 0)
Default
Modify
value
100.0 %
0.0 %
0.0 %
1.0 s
0x0001
Function Parameters

Advertisement

Table of Contents
loading

Table of Contents