Terminal And Entry Data For The Control Cables; Iec - ABB ACH580-01 Hardware Manual

Table of Contents

Advertisement

284 Technical data
ACH580-01-
033A-4
039A-4
046A-4
062A-4
073A-4
089A-4
088A-4
106A-4
145A-4
169A-4
206A-4
246A-4
293A-4
363A-4
430A-4
1) The cable sizing is based on max. 6 cables laid on a cable ladder side by side, ambient temperature 30 °C,
PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364- 5-52/2001). For other conditions,
size the cables according to local safety regulations, appropriate input voltage and the load current of the
drive. See page
278
2) Aluminum cables can be used with U n = 230 V frames R5...R8 only.
Temperature: For IEC, select a cable rated for at least 70 °C maximum permissible
temperature of conductor in continuous use. For North America, power cables must be
rated for 90 °C (194 °F) or higher.
Note: For drives with option +B056 (IP55, UL Type 12), select a cable rated for at least
90 °C (194 °F) maximum permissible temperature of conductor in continuous use.
Voltage: 600 V AC cable is accepted for up to 500 V AC.

Terminal and entry data for the control cables

IEC

Control cable entries, wire sizes and tightening torques (T) are given below.
Frame
Cable entries
size
Holes
pcs
3-phase U n = 230 V
R1
3
Frame size
R3
R3
R3
R4
R4
R4 v2
R5
R5
R6
R7
R7
R8
R8
R9
R9
for the accepted cable sizes of the drive.
Max cable
+24V, DCOM, DGND, EXT.
size
Wire size
mm 2
mm
17
0.2...2.5
Cu cable type
mm 2
3×10 + 10
3×10 + 10
3×10 + 10
3×25 + 16
3×35 + 16
3×50 + 25
3×50 + 25
3×70 + 35
3×95 + 50
3×120 + 70
3×150 + 70
2×(3×70+35)
2×(3×95+50)
2×(3×120+70)
2×(3×150+70)
Control cable entries and terminal sizes
24V terminals
T
N·m
0.5...0.6
1)
AI cable type
mm 2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
DI, AI/O, AGND, RO, STO
terminals
Wire size
mm 2
N·m
0.14...1.5
0.5...0.6
1)
2)
,