Modbus TCP On-Board Communications
Process Data Out 1 to 8
Process Data Out values 1 to 8 can be used in application for
various purposes. See DG1 application manual for what
these values can be set to.
Process Data OUT (Slave R Master)
The fieldbus master can read the AFD's actual values using
process data variables. Standard, Pump and Fan Control, PID
control and Multi-Purpose applications use process data as
follows.
Table 58. Process Data OUT
ID
Data
2104
Process Data OUT 1
2105
Process Data OUT 2
2106
Process Data OUT 3
2107
Process Data OUT 4
2108
Process Data OUT 5
2109
Process Data OUT 6
2110
Process Data OUT 7
2111
Process Data OUT 8
Process Data IN (Master
Control Word, Reference and Process Data are used with
All-in-One applications as follows.
Table 59. Process Data IN
ID
Data
2003
Reference
2001
Control Word
2004
Process Data IN1
2005
Process Data IN2
2006
Process Data IN3
2007
Process Data IN4
2008
Process Data IN5
2009
Process Data IN6
2010
Process Data IN7
2011
Process Data IN8
28
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
Value
–32768~32767
–32768~32767
–32768~32767
–32768~32767
–32768~32767
–32768~32767
–32768~32767
–32768~32767
Slave)
R
Value
Speed Reference
Set point / Feedback / Feedforward for PID
Set point / Feedback / Feedforward for PID
Set point / Feedback / Feedforward for PID
Set point / Feedback / Feedforward for PID
Set point / Feedback / Feedforward for PID
Set point / Feedback / Feedforward for PID
Set point / Feedback / Feedforward for PID
Set point / Feedback / Feedforward for PID
Unit
Scale
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Unit
Scale
Hz
0.01
—
—
%
0.01%
%
0.01%
%
0.01%
%
0.01%
%
0.01%
%
0.01%
%
0.01%
%
0.01%