Table 70. Services Supported By Object Classes; Table 71. Elementary Data Types; Table 72. Constructed Data Types; Table 73. Different Types Of Resets Supported By The Identity Object - Eaton PowerXL DG1 Series VFD Communications Manual

Variable frequency drives
Hide thumbs Also See for PowerXL DG1 Series VFD:
Table of Contents

Advertisement

List of Services
The services supported by these object classes are shown below.

Table 70. Services Supported by Object Classes

Service
Code
(in hex)
Service Name
01
Get_Attributes_All
05
Reset (Type 0 & 1)
0E
Get_Attribute_Single
10
Set_Attribute_Single
4E
Forward Close
52
Unconnected_Send
54
Forward_Open
List of Data Types
The attribute list that follows includes information on the data
type of each attribute. The following tables explain the data,
structure, and array type codes used in the data type column.
Following data types are supported.

Table 71. Elementary Data Types

Data Type
Data Type
Code
Name
(in hex)
BOOL
C1
SINT
C2
INT
C3
USINT
C6
UINT
C7
UDINT
C8
BYTE
D1
WORD
D2
SHORT_STRING
DA
REAL
CA
SHORT_STRING
DA

Table 72. Constructed Data Types

Type Code
Description
A1
Abbreviated array type encoding
A2
Formal structure type encoding
Identity
Connection
TCP/IP
Object
Manager
Interface
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Data Type Description
Logical Boolean with values TRUE and
FALSE
Signed 8-bit integer value
Signed 16-bit integer value
Unsigned 8-bit integer value
Unsigned 16-bit integer value
Unsigned 32-bit integer value
Bit string–8-bit
Bit string–16-bit
Character string (1 byte per character,
1 byte length indicator)
32-bit floating point value
Character string (1 byte per character, 1
byte length indicator)
Ethernet
Link
Assembly
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Reset Service
The following table lists the different types of resets
supported by the identity object.
Resetting the PowerXL interface to its out-of-box
configuration will change the response of the drive to a loss
of communications with the PowerXL. The device will have
to be re-configured for your application before resuming
normal operation. Reset Time 1 sec.
Table 73. Different Types of Resets Supported
by the Identity Object
Value
Type of Reset
0
Initializes drive to the Power-up state.
1
Writes default values to all instance attributes AND then saves
all non-volatile attributes to FLASH memory AND then
performs the equivalent of a Reset (0).
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
EtherNet/IP On-Board Communications
Motor
Control
AC/DC
Data
Supervisor
Drive
Y
Y
Y
Y
Y
Vendor
Parameter
Y
Y
Y
Y
51

Hide quick links: