Table 79. Motor Data Object - Eaton PowerXL DG1 Series VFD Communications Manual

Variable frequency drives
Hide thumbs Also See for PowerXL DG1 Series VFD:
Table of Contents

Advertisement

Motor Data Object, Class 0x28

Table 79. Motor Data Object

ID
Description
Class Attributes
01
Revision
02
Max Instance
03
Number of Instances
Class Services
0Eh
Get_Attribute_Single
Instance 1 Attributes
03h
Motor Type
06h
Rated Current
07h
Rated Voltage
09h
Rated Frequency
0Ch
Pole Count
0Fh
Base Speed
Instance 2 Attributes
03h
Motor Type
06h
First Rated Current
07h
First Rated Voltage
09h
First Rated Frequency
0Ch
Pole Count
0Fh
First Base Speed
Instance 3 Attributes
03h
Motor Type
06h
Second Rated Current
07h
Second Rated Voltage
09h
Second Rated Frequency
0Ch
Pole Count
0Fh
Second Base Speed
Instance Services
0Eh
Get_Attribute_Single
10h
Set_Attribute_Single
Data Type
Access Rule
UINT
Get
UINT
Get
UINT
Get
USINT-V
Get
UINT
Get
UINT
Get
UINT
Get
UINT
Get
UINT
Get
USINT-V
Get
UINT-NV
Get / Set
UINT-NV
Get / Set
UINT-NV
Get / Set
UINT
Get
UINT-NV
Get / Set
USINT-V
Get
UINT-NV
Get / Set
UINT-NV
Get / Set
UINT-NV
Get / Set
UINT
Get
UINT-NV
Get / Set
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
EtherNet/IP On-Board Communications
Remarks/Default Values
1
3
3
Squirrel cage Induction Motor (7)
126,1,5000
380,180,690
50,30,400
4,1,8
1440,300,20000
Squirrel cage Induction Motor (7)
126,1,5000
380,180,690
50,30,400
4,1,8
1440,300,20000
Squirrel cage Induction Motor (7)
120,1,5000
380,180,690
50,30,400
4,1,8
1440,300,20000
57