Process Data Out
This register range is normally used to fast monitoring of the
VFD. Process Data Out is located in range ID 2101–2199.
See table below.

Table 54. Fieldbus Basic Output Table

ID
Modbus Register
Group
2101
32101, 42101
FB Status Word
2102
32102, 42102
FB General Status Word
2103
32103, 42103
FB Actual Speed
2104
32104, 42104
FB Process Data Out 1
2105
32105, 42105
FB Process Data Out 2
2106
32106, 42106
FB Process Data Out 3
2107
32107, 42107
FB Process Data Out 4
2108
32108, 42108
FB Process Data Out 5
2109
32109, 42109
FB Process Data Out 6
2110
32110, 42110
FB Process Data Out 7
2111
32111, 42111
FB Process Data Out 8

Table 55. Status Word

15 14 13 12 11 10 9 8
— — — — — — — — RUNEN BYS AREF WARN FLT DIR RUN RDY
Range/Type
Binary coded
Binary coded
Hz
7
6
5
4
3
2
Modbus TCP On-Board Communications
Information about the status of the device and messages is
indicated in the Status Word. The Status Word is composed
of 16 bits that have the following meanings.

Table 56. Status Word Bit Descriptions

Description
Bit
Value = 0
0
Not Ready
1
STOP
2
Clockwise
3
4
5
Ref. frequency not reached
6
Bypass not activated
7
Run disable
8
Not in use
9–15
Not in use

Table 57. Actual Speed

15
14 13 12 11 10
MSB — — — — — — — — — — — — — — LSB
1
0
This is the Actual Speed of the motor.
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
Value = 1
Ready
RUN
Counterclockwise
Faulted
Warning
Ref. frequency reached
Bypass activated
Run Enable
Not in use
Not In use
9
8
7
6
5
4
3
2
1
0
27