Commissioning; Figure 9. Keypad Navigation To Rs-485 Menu - Eaton PowerXL DG1 Series VFD Communications Manual

Variable frequency drives
Hide thumbs Also See for PowerXL DG1 Series VFD:
Table of Contents

Advertisement

Modbus RTU On-Board Communications

Commissioning

RS-485 Communication Parameters
To commission the RS-485 communication board, enter the
Keypad menu as described below.
Change the Modbus RTU commissioning parameter values.

Figure 9. Keypad Navigation to RS-485 Menu

In this menu you will be able to scroll through the below
settings to setup the communication protocol.
Table 7. Modbus RTU/BACnet MS/TP—P20.2
Code
Parameter
P20.2.1
RS485 Comm Set
P20.2.2
Slave Address
P20.2.3
Baud Rate
P20.2.4
Parity Type
P20.2.5
Protocol Status
8
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
Min.
Max.
Unit
1
247
Default
ID
Note
0
586
0 = Modbus RTU
1 = BACnet
18
587
2
584
0 = 9600
1 = 19200
2 = 38400
3 = 57600
4 = 115200
2
585
0 = None
1 = Odd
2 = Even
0
588
0 = Initial
1 = Stopped
2 = Operational
3 = Faulted
®
MS/TP