Assembly Instance 107

Table 92. Instance 107 (Input) Length = 8 Bytes

Byte
Bit 7
Bit 6
0
AtReference RefFromNet CtrlFromNet Ready
1
Drive State
1
2
% Speed Actual (Low Byte)
3
% Speed Actual (High Byte)
4
Process DataOut1 (Low Byte)
5
Process DataOut1 (High Byte)
6
Process DataOut2 (Low Byte)
7
Process DataOut2 (High Byte)
1
Refer "State transition diagram" , provided under "Control Supervisor Object" and "Drive State"
table specified at end of "Input Instances" section.
Drive State
0x00
DN_NON_EXISTANT
0x01
DN_STARTUP
0x02
DN_NOT_READY
0x03
DN_READY
0x04
DN_ENABLED
0x05
DN_STOPPING
0x06
DN_FAULT_STOP
0x07
DN_FAULTED
2
Speed Actual. This is the actual value from the frequency converter. The value is between
0 and 10000. In the application, the value is scaled in percentage of frequency area between
set minimum and maximum frequency. (0 = 0.00%–10000 = 100.00%).
66
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
Bit 5
Bit 4
Bit 3
Running2
2
2
Bit 2
Bit 1
Bit 0
Running1
Warning
Faulted