EtherNet/IP On-Board Communications
Assembly Instance 101
Table 87. Instance 101 (Output) Length = 8 Bytes
Byte
Bit 7
Bit 6
0
NetRef
1
2
FBSpeed Reference (Low Byte), rpm
3
FBSpeed Reference (High Byte), rpm
4
FBProcessDataIn1 (Low Byte)
5
FBProcessDataIn1 (High Byte)
6
FBProcessDataIn2 (Low Byte)
7
FBProcessDataIn2 (High Byte)
Note: Process data is sent to the drive independently from the NetRef and NetCtrl bits settings.
Assembly Instance 111
Table 88. Instance 111 (Output) Length = 20 Bytes
Byte
Bit 7
Bit 6
0
FBFixedControlWord (Low Byte)
1
FBFixedControlWord (High Byte)
2
FBSpeedReference (Low Byte)
3
FBSpeedReference (High Byte)
4
ProcessDataIn1 (LowByte)
5
ProcessDataIn1 (HighByte)
6
ProcessDataIn2 (LowByte)
7
ProcessDataIn2 (HighByte)
8
ProcessDataIn3 (LowByte)
9
ProcessDataIn3 (HighByte)
10
ProcessDataIn4 (LowByte)
11
ProcessDataIn4 (HighByte)
12
ProcessDataIn5 (LowByte)
13
ProcessDataIn5 (HighByte)
14
ProcessDataIn6 (LowByte)
15
ProcessDataIn6 (HighByte)
16
ProcessDataIn7 (LowByte)
17
ProcessDataIn7 (HighByte)
18
ProcessDataIn8 (LowByte)
19
ProcessDataIn8 (HighByte)
1
FBFixedControlWord.
Bit
Description (Value = 0)
0
STOP
1
Clockwise
2
Rising edge of this bit will reset active fault
3–15
Not in use
2
This is the reference1 to the frequency converter. Used normally as Speed reference. The allowed scaling
is 0...10000. In the application, the value is scaled in percentage of the frequency area between set
minimum and maximum frequency. (0 = 0.00%–10000 = 100.00%).
64
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
Bit 5
Bit 4
Bit 3
NetCtrl
Bit 5
Bit 4
Bit 3
1
1
2
2
Description (Value = 1)
RUN
Counter-clockwise
Rising edge of this bit will reset active fault
Not in use
Bit 2
Bit 1
Bit 0
FaultReset
RunRev
RunFwd
Bit 2
Bit 1
Bit 0
Default Range
0
0–1
0
0–1
0
0–1
0
0