Modbus Registers
The variables and fault codes as well as the parameters can
be read and written from Modbus. The parameter addresses
are determined in the application. Every parameter and actual
value have been given an ID number in the application. The
ID numbering of the parameter as well as the parameter
ranges and steps can be found in the application manual in
question. The parameter value shall be given without
decimals.
All values can be read with function codes 3 and 4 (all
registers are 3X and 4X reference). Modbus registers are
mapped to drive IDs as follows.

Table 20. Index Table

ID
Modbus Register
1–98
40001–40098
(30001–30098)
99
40099 (30099)
101–1999
40101–41999
(30101–31999)
2001–2099
42001–42099
(32001–32099)
2101–2199
42101–42199
(32101–32199)
Group
R/W
Actual Values
1/1
Fault Code
1/1
Parameters
1/1
Process Data In
20/20
Process Data Out
20/20
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
Modbus RTU On-Board Communications
Process Data
The process data fields are used to control the drive (e.g.,
Run, Stop, Reference, Fault Reset) and to quickly read actual
values (e.g., Output frequency, Output current, Fault code).
The fields are structured as follows.

Table 21. Process Data Slave R Master (max. 22 bytes)

ID
Modbus Register
Group
2101
32101, 42101
FB Status Word
2102
32102, 42102
FB General Status Word
2103
32103, 42103
FB Actual Speed
2104
32104, 42104
FB Process Data Out 1
2105
32105, 42105
FB Process Data Out 2
2106
32106, 42106
FB Process Data Out 3
2107
32107, 42107
FB Process Data Out 4
2108
32108, 42108
FB Process Data Out 5
2109
32109, 42109
FB Process Data Out 6
2110
32110, 42110
FB Process Data Out 7
2111
32111, 42111
FB Process Data Out 8

Table 22. Process Data Master R Slave (max. 22 bytes)

ID
Modbus Register
Group
2001
32001, 42001
FB Control Word
2002
32002, 42002
FB General Control Word
2003
32003, 42003
FB Speed Reference
2004
32004, 42004
FB Process Data In 1
2005
32005, 42005
FB Process Data In 2
2006
32006, 42006
FB Process Data In 3
2007
32007, 42007
FB Process Data In 4
2008
32008, 42008
FB Process Data In 5
2009
32009, 42009
FB Process Data In 6
2010
32010, 42010
FB Process Data In 7
2011
32011, 42011
FB Process Data In 8
The use of process data depends on the application. In a
typical situation, the device is started and stopped with the
Control Word (CW) written by the Master and the Rotating
speed is set with Reference (REF). With PD1–PD8 the device
can be given other reference values (e.g., Torque reference).
With the Status Word (SW) read by the Master, the status of
the device can be seen. Actual Value (ACT) and PD1–PD8
show the other actual values.
Range/Type
Binary coded
Binary coded
0–100.00%
Range/Type
Binary coded
Binary coded
0–100.00% Hz
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
13