PROFIBUS-DP External Communication Cards
Figure 37. Com1 PROFIBUS DB9 Adapter
PROFIBUS Cable
Two types of cables can be used for PROFIBUS connection.
Table 104. PROFIBUS Cable Connections
Parameter
Line A
Impedance
135–165 Ω (3–20 MHz)
Capacity
<30 pF/m
Resistance
<100 Ω/km
Wire gauge
>0.64 mm
2
Conductor area
>0.34 mm
Table 105. Recommended Cable
Cable
Description
Belden
PROFIBUS Data Cable
Olflex
PROFIBUS Cable
Siemens
SINEC L2 LAN cable for PROFIBUS
82
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
Line B
100–130 Ω (f >100 kHz)
<60 pf/m
—
>0.53 mm
2
>0.22 mm
Part Number
3079A
21702xx
6XV1830=0AH0