Table 109. Control Word (Stw1) - Eaton PowerXL DG1 Series VFD Communications Manual

Variable frequency drives
Hide thumbs Also See for PowerXL DG1 Series VFD:
Table of Contents

Advertisement

PROFIBUS-DP External Communication Cards
Table 108. PROFIdrive Control Word 1—STW1, continued
Bit
Value
Significance
10
1
Control By PLC
0
No Control By PLC
11
1
Device Specific
0
Device Specific
12
1
Device Specific
0
Device Specific
13
1
Device Specific
0
Device Specific
14
1
Device Specific
0
Device Specific
15
1
Device Specific
0
Device Specific
Below is various defined control word (STW1) command.

Table 109. Control Word (STW1)

Control
Word
SN
(STW1)
Control Word Description (STW1)
1
0x0400
Set PLC Control
2
0x0000
Clear PLC Control
3
0x040F
Run Command without RFG
4
0x0407
Clear Run Command
5
0x041F
Run Command with RFG and without Set point
6
0x0407
Clear Run Command
7
0x047F
Run Command with RFG and with Set point
8
0x0407
Clear Run Command
9
0x047F
Run Command with RFG and with Set point
10
0x045F
Set Freeze of Ramp
11
0x047F
Clear Freeze of Ramp
12
0x047E
OFF 1 Command
13
0x047F
Run Command with RFG and with Set point
14
0x047D
OFF 2 Command (Coast Stop)
15
0x047F
Run Command with RFG and with Set point
16
0x047B
OFF 3 Command (Quick Stop)
17
0x047F
Run Command with RFG and with Set point
18
0x0477
Disable Operation
19
0x057F
Run Command with RFG and with Set point At Jog Speed
20
0x0477
Disable Operation
21
0x0480
Fault Reset bit
88
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
Comments
Control via interface, DO I/O Data valid (refer to 6.3.11).
DO I/O Data not valid; expect Sign-Of-Life. If loosing the control priority bit the reaction is
device-specific. Possible reactions.
1) speed control. "old" process data is kept,
2) positioning. DO I/O Data are set to 0.
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Comment
PLC Control should be set in MCU
PLC Control should be reset in MCU
Motor Off as no RAMP Generator
Motor Off as earlier
Motor Off as no Set point Generator
Motor Off as earlier
Motor ON with RFG
Motor Off as earlier
Motor ON with RFG
Motor ON with Ramp Freeze
Motor ON with Following Ramp Timing
Motor Off with RFG
Motor ON with RFG
Motor Off with Coast
Motor ON with RFG
Motor Off with 0 DECEL Time
Motor ON with RFG
Motor Off with Coast
Motor ON at Jog Speed
Motor Off with Coast
Fault should get reset