Table 110. Application Status Word Profidrive - Eaton PowerXL DG1 Series VFD Communications Manual

Variable frequency drives
Hide thumbs Also See for PowerXL DG1 Series VFD:
Table of Contents

Advertisement

Status Word 1 (ZSW1)

Table 110. Application Status Word PROFIdrive

Bit
Value
Significance
0
1
Ready To Switch On
0
Not Ready To Switch On
1
1
Ready To Operate
0
Not Ready To Operate
2
1
Operation Enabled
0
Operation Disabled
3
1
Fault Present
0
No Fault
4
1
Coast Stop Not Activated
(No OFF 2)
0
Coast Stop Activated
(OFF 2)
5
1
Quick Stop Not Activated
(No OFF 3)
0
Quick Stop Activated
(OFF 3)
6
1
Switching On Inhibited
0
Switching On Not Inhibit
7
1
Warning Present
0
No Warning
8
1
Speed Error Within Tolerance
Range
0
Speed Error Out Of Tolerance
Range
9
1
Control Requested
0
No Control Requested
10
1
f Or n Reached Or Exceeded
0
f Or n Not Reached
11
1
Device Specific
0
Device Specific
12
1
Device Specific
0
Device Specific
13
1
Device Specific
0
Device Specific
Comments
Power supply is switched on, electronics initialized, main contact, if available, has dropped out, pulses
are inhibited.
Refer to control word 1, bit 0.
Drive follows set point. This means, that the electronic and pulses are enabled (Refer to control word 1,
bit 3), the closed loop control is active and controls the motor and the output of the set point channel is
the input for the closed loop control.
Either the pulses are disabled or the drive doesn't follow the output value of the set point channel.
Unacknowledged faults or currently not acknowledgeable faults (fault messages) are present (in the
fault buffer). The fault reaction is fault-specific and device-specific. The acknowledging of a fault may
only be successful, if the fault cause has disappeared or has been removed before. If the fault has
isolated the voltage, the drive goes into the "Switching On Inhibited" condition, otherwise the drive
returns to operation. The related fault numbers are in the fault buffer.
"Coast Stop (OFF 2)" command is present.
"Quick Stop (OFF 3)" command is present.
The drive goes only again in the "Switched On" condition with "No Coast Stop AND No Quick Stop"
followed by "ON". This means that the "Switching On Inhibited" bit is only set back to zero if the OFF
command is set after "No Coast Stop AND No Quick Stop."
Warning information present in the service/maintenance parameter; no acknowledgement.
There is no warning or the warning has disappeared again.
Actual value is within a tolerance band; dynamic violations are permissible for t < tmax, e.g.,
n=nset±,
f=fset±, etc.,
tmax may be parameterised
The automation system is requested to assume control (refer to 6.3.11.
Control by the automation system is not possible, only possible at the device or by another interface.
Actual value ≥ comparison value (set point) which may be set via the parameter number.
N/A
N/A
N/A
N/A
N/A
N/A
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
PROFIBUS-DP External Communication Cards
89