Table 117. Field Coding - Eaton PowerXL DG1 Series VFD Communications Manual

Variable frequency drives
Hide thumbs Also See for PowerXL DG1 Series VFD:
Table of Contents

Advertisement

PROFIBUS-DP External Communication Cards
Coding
Coding of the fields in parameter request/parameter
response of base model parameter access.

Table 117. Field Coding

Field
Data Type
Request Reference
Unsigned 8
Response ID
Unsigned 8
Axis/DO-ID
Unsigned 8
No. of Parameters
Unsigned 8
Attribute
Unsigned 8
No. of Elements
Unsigned 8
Parameter Number
Unsigned 16
Subindex
Unsigned 16
94
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
Values
0x00
Reserved
0x01...0xFF
0x00
Reserved
0x01
Request parameter (+)
0x02
Change parameter(+)
0x03...0x3F
Reserved
0x40...0x7F
Manufacturer-specific
0x80
Reserved
0x81
Request parameter (–)
0x82
Change parameter (–)
0x83...0xBF
Reserved
0xC0...0xFF
Manufacturer-specific
0x00
Device-Representative
0x01...0xFE
DO-ID-Number 1–254
0xFF
Reserved
0x00
Reserved
0x01...0x27
Quantity 1–39
0x28...0xFF
Reserved
0x00
Reserved
0x10
Value
0x20
Description
0x30
Text
0x40...0x70
Reserved
0x80...0xF0
Manufacturer-specific
0x00
Special Function
0x01...0xEA
Quality 1–234
0xEB...0xFF
Reserved
0x0000
Reserved
0x0001
Number 1–65535
0xFFFF
0x0000...
Number 0–65534
0xFFFF
Comment
Zero is not a DO but representative of the access to the
drive unit.
There may be an additional limitation through the
communication system (telegram length) or optional
scalability.
The four less significant bits are reserved for (future)
expansion of "No. of Elements" to 12 bits.
Limitation through compatibility with PROFIBUS process
data ASE telegram length.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents