Table 89. Instance 70 (Input) Length = 4 Bytes; Table 90. Instance 71 (Input) Length = 4 Bytes; Table 91. Instance 73 (Input) Length = 6 Bytes - Eaton PowerXL DG1 Series VFD Communications Manual

Variable frequency drives
Hide thumbs Also See for PowerXL DG1 Series VFD:
Table of Contents

Advertisement

Input Instances
Assembly Instance 70

Table 89. Instance 70 (Input) Length = 4 Bytes

Byte
Bit 7
Bit 6
0
1
2
Speed Actual (Low Byte), rpm
3
Speed Actual (High Byte), rpm
Assembly Instance 71

Table 90. Instance 71 (Input) Length = 4 Bytes

Byte
Bit 7
Bit 6
0
AtReference RefFromNet CtrlFromNet Ready
1
Drive State
1
2
Speed Actual (Low Byte), rpm
3
Speed Actual (High Byte), rpm
1
Refer "State transition diagram" , provided under "Control Supervisor Object" and "Drive State"
table specified at end of "Input Instances" section.
Assembly Instance 73

Table 91. Instance 73 (Input) Length = 6 Bytes

Byte
Bit 7
Bit 6
0
AtReference RefFromNet CtrlFromNet Ready
1
Drive State
1
2
Speed Actual (Low Byte), rpm
3
Speed Actual (High Byte), rpm
4
Torque Actual (Low Byte), Nm
5
Torque Actual (High Byte), Nm
1
Refer "State transition diagram" , provided under "Control Supervisor Object" and "Drive State"
table specified at end of "Input Instances" section.
Bit 5
Bit 4
Bit 3
Bit 5
Bit 4
Bit 3
Running2
Bit 5
Bit 4
Bit 3
Running2
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
EtherNet/IP On-Board Communications
Bit 2
Bit 1
Bit 0
Running1
Faulted
Bit 2
Bit 1
Bit 0
Running1
Warning
Faulted
Bit 2
Bit 1
Bit 0
Running1
Warning
Faulted
65