Description
3.5 Operating modes and master control function
3.5
Operating modes and master control function
3.5.1
Operating modes
Control source and motor control
The operating modes assign access rights to the various control sources (access sources). The
control source that possesses the rights for controlling and writing access has control. As only
one control source can ever have control at one time, different priorities are assigned to the
operating modes. Read access is also possible without control.
①
②
③
④
⑤
⑥
24
Control source: 3RW5 HMI, operating mode: Manual operation local - HMI controlled
Control source: Input IN or digital inputs, operating mode: Manual operation local - input con‐
trolled or Automatic - input controlled
Control source: Web server, operating mode: Manual operation bus - Webserver controlled
Control source: PLC, operating mode: Automatic
Control source: SIRIUS Soft Starter ES (TIA Portal) Premium / Professional, operating mode: Man‐
ual operation bus - PC controlled
Control source: SIRIUS Soft Starter ES (TIA Portal), operating mode: Manual operation local - PC
controlled
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004