17.3 Commissioning aids
17.3.1 Simulation of outside temperature
To facilitate commissioning and fault tracing, outside temperatures in the range
from 50 to 50 °C can be simulated. Simulation has an impact on the current, the
composite and the attenuated outside temperature.
Simulated T
= current T
A
During the simulation, the current outside temperature (as acquired by the sensor
or via LPB) is overridden.
When simulation is completed, the current outside temperature gradually readjusts
the composite and the attenuated outside temperature to their correct values.
Hence, simulation of the outside temperature leads to a reset of the attenuated and
the composite outside temperature.
Simulation can be ended in one of 3 different ways:
By entering --.-
By leaving the setting level by pressing any of the operating mode buttons
Automatically after 30 minutes
17.3.2 Relay test
The output relays can be individually energized. The following coding applies:
Input
Relay test
0
Normal operation (no test)
1
All relays deenergized
2
Burner stage 1 ON
3
Burner stages 1 and 2 ON
4
Heating circuit pump ON
5
Storage tank charging pump ON
6
Actuator heating circuit 1 OPEN
7
Actuator heating circuit 1 CLOSE
8
Heating circuit pump heating circuit
1 ON
9
Heating circuit pump heating circuit
2 ON
10
Multi-functional relay energized
11
Actuator heating circuit 2 OPEN
12
Actuator heating circuit 2 CLOSE
The relay test can be ended in one of 4 different ways:
By entering 0 on the operating line
By leaving the setting level by pressing
By leaving the setting level by pressing any of the operating mode buttons
Automatically after 30 minutes
Basic Documentation RVP360
17 Function block: Service functions and general settings
= composite T
= attenuated T
A
A
or
A
Relay
–
–
K4
K4 and K5
Q1
Q3
Y1
Y2
Q2
Q6
K6
Y7
Y8
CE1P2546en
2017-07-24