Figure 4-13. Distributed Bypass Wire Length - Eaton Power Xpert 9395 Installation And Operation Manual

Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

Bypass Input to UPS Units
1A
2A
3A
4A
NOTE Required parallel system wiring length must be equal to ensure approximately equal current sharing when in Bypass mode. For proper
operation the following must be true:
1A = 2A = 3A = 4A
1B = 2B = 3B = 4B

Figure 4-13. Distributed Bypass Wire Length

®
®
Eaton
Power Xpert
9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual
UPS 1
Battery
UPS 2
Battery
UPS 3
Battery
UPS 4
Battery
P-164000563—Rev 04 www.eaton.com/powerquality
Installation
Output from UPS Units
1B
2B
3B
4B
4-17

Advertisement

Table of Contents
loading

Table of Contents