Powerware Series ® Eaton 9395 UPS, Plus 1 UPS, and 825/550 UPS 450–825 kVA Installation and Operation Manual For use with Two UPM (450–550 kVA), Three UPM (650–825 kVA), and Plus 1 (650–825 kVA) UPS Models...
Page 3
Powerware Series ® Eaton 9395 UPS, Plus 1 UPS, and 825/550 UPS 450–825 kVA Installation and Operation Manual For use with Two UPM (450–550 kVA), Three UPM (650–825 kVA), and Plus 1 (650–825 kVA) UPS Models...
National Fire Protection Association, Inc. All other trademarks are property of their respective companies. ECopyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
Power Management Software LanSafe Power Management Software is bundled as part of the Software Suite CD ® shipped with the UPS. See Chapter 8, “Communication,” for additional information. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
1.2.1 Field Installed UPM A Field Installed UPM (FI-UPM) provides upgradability for the Eaton 9395 825/550 two UPM UPS. The FI-UPM may be installed at any time in the future when power needs change. The module cabinet is installed on the left side of the ISBM section and is wired directly to the UPS.
1.2.8 Inherent Redundancy To deliver greater reliability, the Eaton 9395 UPS can be configured by an authorized Eaton Customer Service Engineer for inherent redundancy. When configured, the UPS automatically becomes redundant if the load is at or below the capacity of the UPMs minus the capacity of one UPM.
A ConnectUPS -X Web/SNMP Card is required in an X-Slot communication bay. An optional Environmental Monitoring Probe (EMP) is required for temperature/humidity monitoring. See Chapter 8, “Communication,” for additional information on monitoring and communication features. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
825 kVA ISBM, three UPM, Continuous Static Switch (CSS) 825 kVA ISBM, four UPM (Plus 1), CSS 825 kVA IOM, three UPM 825 kVA IOM, four UPM (Plus 1) 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
INTRODUCTION Using This Manual This manual describes how to install and operate the Eaton 9395 450–825 kVA UPS. Read and understand the procedures described in this manual to ensure trouble-free installation and operation. In particular, be thoroughly familiar with the REPO procedure (see paragraph 7.3.25 on page 7-29).
(WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. For More Information Refer to the Eaton 9390 and 9395 Sync Control Installation and Operation Manual for the following additional information: Installation instructions, including site preparation, planning for installation, and wiring and safety information.
A question this manual does not answer Please call the Help Desk at: 1-800-843-9433 1-919-870-3028 United States: 1-800-461-9166 ext 260 Canada: Call your local service representative All other countries: 1-11 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 24
INTRODUCTION This page intentionally left blank. 1-12 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Keep the UPS door closed and front panels installed to ensure proper cooling airflow and to protect personnel from dangerous voltages inside the unit. Do not install or operate the UPS system close to gas or electric heat sources. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 26
Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans votre localité. Ne jamais jeter les batteries au feu. L'exposition aux flammes risque de les faire exploser. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
Page 30
914.4 mm (36”) working space From Back of Cabinet None Required From Right Side of 152.4 mm (6”) working space Cabinet From Left Side of Cabinet None Required 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
UPS INSTALLATION PLAN AND UNPACKING Front Dimensions are in millimeters [inches]. Figure 3‐7. ISBM Section Dimensions (Top View) Front Dimensions are in millimeters [inches]. Figure 3‐8. ISBM Section Dimensions (Bottom View) 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Dimensions are in millimeters [inches]. Figure 3‐13. UPM Section Center of Gravity – Three UPM Dimensions are in millimeters [inches]. Figure 3‐14. UPM Section Center of Gravity – Two UPM 3-10 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
The bypass feed into this equipment uses three or four wires. The rectifier feed into this equipment uses three wires. The phases must be symmetrical about ground (from a Wye source) for proper equipment operation. 3-11 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 40
A Field Installed UPM (FI-UPM) is always designated as UPM 4. The Eaton 9395-825/550 two UPM UPS is upgradable to a fully rated 825 kVA with the addition of the FI-UPM. Because of this future upgradability, the UPS wire and external overcurrent protection ratings listed in the following tables are specified for 825 kVA.
Page 41
Because of the future upgradability to a fully rated 825 kVA UPS with the addition of the FI-UPM, the UPS wiring is specified for 825 kVA in Table 3‐6 and Table 3‐7. Wire sizes listed are for copper wiring only. 3-13 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 42
UPS INSTALLATION PLAN AND UNPACKING Table 3‐4. Input/Output Ratings and External Wiring Requirements for the Three UPM Eaton 9395-825/650, 9395-825/750, and 9395-825/825 – Common Battery Units Rating 50/60 Hz Basic Unit Rating Input and Output Voltage Volts 400/400 480/480 400/400...
Page 43
UPS INSTALLATION PLAN AND UNPACKING Table 3‐5. Input/Output Ratings and External Wiring Requirements for the Three UPM Eaton 9395-825/650, 9395-825/750, and 9395-825/825 – Separate Battery Units Rating 50/60 Hz Basic Unit Rating Input and Output Voltage Volts 400/400 480/480 400/400...
Page 44
UPS INSTALLATION PLAN AND UNPACKING Table 3‐6. Input/Output Ratings and External Wiring Requirements for the Two UPM Eaton 9395-825/450, 9395-825/500, and 9395-825/550 – Common Battery Units Rating 50/60 Hz Basic Unit Rating Input and Output Voltage Volts 400/400 480/480 400/400...
Page 45
UPS INSTALLATION PLAN AND UNPACKING Table 3‐7. Input/Output Ratings and External Wiring Requirements for the Two UPM Eaton 9395-825/450, 9395-825/500, and 9395-825/550 – Separate Battery Units Rating 50/60 Hz Basic Unit Rating Input and Output Voltage Volts 400/400 480/480 400/400...
Page 46
UPS (see Table 3‐5 or Table 3‐7). Table 3‐8. Separate Rectifier Input UPM Ratings and External Wiring Requirements for the Three UPM Eaton 9395-825/650, 9395-825/750, and 9395-825/825 and the Two UPM Eaton 9395-825/450, 9395-825/500, 9395-825/550 – Separate Battery...
Page 47
Figure 4‐10 through Figure 4‐17 starting on page 4-14 show the location of the intercabinet power cable terminals inside the UPS. Table 3‐9. UPS Intercabinet Power Cable Terminations for the Three UPM Eaton 9395-825/650, 9395-825/750, and 9395-825/825 and the Two UPM Eaton 9395-825/450, 9395-825/500, 9395-825/550...
Page 48
Figure 4‐25 through Figure 4‐33 starting on page 4-31 show the location of the power cable terminals inside the UPS. Table 3‐11. UPS External Power Cable Terminations for the Three UPM Eaton 9395-825/650, 9395-825/750, and 9395-825/825 and the Two UPM Eaton 9395-825/450, 9395-825/500, 9395-825/550...
Page 49
Thomas & Betts TBM14M Die Set Thomas & Betts 15506 Table 3‐14. Separate Rectifier Input UPM Power Cable Terminations for the Three UPM Eaton 9395-825/650, 9395-825/750, and 9395-825/825 and the Two UPM Eaton 9395-825/450, 9395-825/500, 9395-825/550 Tightening Torque Terminal Function Terminal...
Page 50
AC Input to Bypass and Output (Four Wire) (A, B, C, Ground) AC Input to Bypass and Output (Five Wire) (A, B, C, Neutral, Ground) Battery See Note 1 (Positive, Negative, Ground) 3-22 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 51
NOTE 2 Because of the future upgradability to a fully rated 825 kVA UPS with the addition of the FI-UPM, these conduit sizes are specified for an 825kVA UPS. NOTE 3 Bypass conduit data is not applicable to IOM configurations. 3-23 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 52
NOTE Because of the future upgradability to a fully rated 825 kVA UPS with the addition of the FI-UPM, these breaker sizes are specified for an 825 kVA UPS. 3-24 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 53
Recommended disconnect size is based on a maximum full load discharge time less than 3 hours. For longer discharge times a larger disconnect may be required. 3-25 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 54
The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC voltage at rated battery current. 3-26 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
A jumper wire must be connected between pins 1 and 2 on TB1, if the normally‐closed REPO contact is not used. REPO wiring should be a minimum of 22 AWG and a maximum of 14 AWG. 3-27 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
With dual auxiliary MOBs, one UPM can be bypassed while the remaining UPMs support the load as long as the remaining UPMs have the capacity to do so. 3-28 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Carefully inspect the outer packaging for evidence of damage during transit. C A U T I O N Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. NOTE For the following step, verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see Table 3‐1 on page 3-2 for cabinet weight).
Inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading. If damage has occurred or shortages are evident, contact an Eaton service representative immediately to determine the extent of the damage and its impact on further installation.
End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no upward angling. If these instructions are not followed, damage to the wiring channel and wiring will occur. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Figure 4‐6). Remove the right side shipping bracket. Front Door Pallet Shipping Bracket Bolts Shipping Bracket Left Side Shipping Bolts Bracket Figure 4‐1. Removing the ISBM Section Left Side Shipping Bracket 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Carefully lower the cabinet until the cabinet base contacts the floor. Repeat Steps 2 through 6 for the remaining cabinet. Proceed to paragraph 4.3. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
UPS SYSTEM INSTALLATION Pallet Shipping Bracket Bolts Right Side Shipping Bracket Shipping Bracket Bolts Figure 4‐4. Removing the Three UPM Section Right Side Shipping Bracket 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Retain the hardware for later use. Remove the screws securing the corner channel and remove the channel (see Figure 4‐7). Retain the hardware for later use. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Reinstall the corner channel (see Figure 4‐7) and secure using the retained hardware. Reinstall the left middle panel (see Figure 4‐7) and secure using the retained hardware. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
ISBM and UPM sections. Secure the bracket with the screws from the hardware kit (see Figure 4‐9). 13. Proceed to paragraph 4.4. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Locate the AC and DC input intercabinet power wiring harnesses (long cables labeled xG1, xG2, and xG3). Remove wire ties as necessary and uncoil the cables. 4-10 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 71
NOTE AC output intercabinet power wiring harnesses are supplied attached to the interior left side panel of the UPM section (see Figure 4‐7 on page 4-8). 4-11 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 72
NOTE The 3G4 and 3G4 yellow, orange, brown, and gray AC output intercabinet power wiring harnesses are not supplied with the Eaton 9395-825/550 Two UPM UPS model. 10. Locate the 1G4, 1G5, 2G4, 2G5, 3G4, and 3G5 power wiring harnesses. Remove the front two columns of wire ties securing the cables to facilitate routing cables to the AC Output from UPMs terminals.
Page 73
26. If installing a battery system, proceed to paragraph 4.6; otherwise, proceed to Step 27. 27. If installing a tie cabinet or distribution panel for a distributed bypass system, proceed to paragraph 4.7; otherwise, proceed to paragraph 4.8. 4-13 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
NOTE On a UPS configured as an Input Output Module (IOM), UPM input wiring terminations are the same as an ISBM configuration. Figure 4‐11. ISBM Section Input Power Terminal Detail – Common Rectifier Feed, Momentary Static Switch 4-15 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Install the second lug with the raised barrel portion facing the front of the cabinet. Figure 4‐13. ISBM Section Input Power Terminal Detail – Continuous Static Switch 4-17 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
NOTE On a UPS configured as an Input Output Module (IOM), UPM input wiring terminations are the same as an ISBM configuration. Figure 4‐15. ISBM Section Input Power Terminal Detail – Separate Rectifier Feed, Momentary Static Switch 4-19 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Install the second lug with the raised barrel portion facing the front of the cabinet. Figure 4‐17. ISBM Section Output Power Terminal Detail 4-20 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
If installing a Plus 1 model or adding the FI-UPM to an 825/550 model, install the FI-UPM using the instructions in the Eaton 9395 Field Installed UPM Mechanical Installation Manual, listed in paragraph 1.8 on page 1-10. After the FI-UPM is installed, proceed to paragraph 4.6 if installing a battery system;...
NOTE On a UPS that is configured for separate rectifier inputs, all sources that feed the separate rectifier inputs must be derived from a common ground point. 4-25 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 86
Three UPM Section Front Ventilation Grill Debris Shields (Remove shields before operating system.) Two UPM Section Front Figure 4‐22. ISBM and UPM Section Debris Shields 4-26 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 87
Bottom Entry Conduit Landing for AC Input and Output, and DC Input (Remove panel to drill or punch conduit holes.) Figure 4‐23. ISBM Section Conduit and Wire Entry Locations 4-27 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 88
See paragraph 3.2.2 on page 3-11 for wiring and termination requirements. 15. Proceed to paragraph 4.8.3. 4-28 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 89
NOTE Any difference in wire length will result in decreased capacity of the UPS system while on bypass. For example, a 10% difference between the longest and shortest wire lengths will result in a decrease in bypass capacity of 10%. Figure 4‐24. Distributed Bypass Wire Length 4-29 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 90
NOTE AC Input to Bypass terminals are not applicable to an IOM configuration. Figure 4‐25. ISBM Section Power Terminal Locations – Common Rectifier Feed, Momentary Static Switch 4-30 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 91
NOTE AC Input to Bypass terminals are not applicable to an IOM configuration. Figure 4‐26. ISBM Section Power Terminal Detail AA – Common Rectifier Feed, Momentary Static Switch 4-31 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 92
NOTE AC Input to Bypass terminals are not applicable to an IOM configuration. Figure 4‐27. ISBM Section Power Terminal Locations – Common Rectifier Feed, Continuous Static Switch 4-32 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 93
AC Input to Phase B (E7) UPS Bypass Phase C (E8) Section A–A Figure 4‐28. ISBM Section Power Terminal Detail AA – Common Rectifier Feed, Continuous Static Switch 4-33 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 94
NOTE AC Input to Bypass terminals are not applicable to an IOM configuration. Figure 4‐29. ISBM Section Power Terminal Locations – Separate Rectifier Feed, Momentary Static Switch 4-34 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 95
NOTE AC Input to Bypass terminals are not applicable to an IOM configuration. Figure 4‐30. ISBM Section Power Terminal Detail AA – Separate Rectifier Feed, Momentary Static Switch 4-35 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 96
Phase A (E1A) AC Input to Phase B (E2A) UPM 4 (FI-UPM Phase C (E3A) Figure 4‐31. UPM Rectifier Input Power Terminal Block Detail, Momentary Static Switch 4-36 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
4.8.2, Step 2 on page 4-25. Secure with the retained hardware. Reinstall the left front panel removed in paragraph 4.8.2, Step 1 on page 4-25 and secure with the retained hardware. 4-37 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 98
DC Input from Battery + (E4) Front DC Input from Battery – (E5) Section B–B Figure 4‐32. ISBM Section Power Terminal Detail BB – Common Battery 4-38 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 99
DC Input from Battery – (E5) (UPM 3) (Not used with Two UPM systems.) Section B–B Figure 4‐33. ISBM Section Power Terminal Detail BB – Separate Battery 4-39 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
X-Slot connections only, proceed to paragraph 4.9.3; otherwise, proceed to Step 10. 10. Reinstall the top internal safety shield panel and secure with the retained hardware. 4-40 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 101
(See Figure 4‐35 page 4-47 for detail.) for detail.) (See Figure 4‐37 on page 4-44 for terminal assignments.) ISBM Figure 4‐34. ISBM Section Interface Terminal Locations 4-41 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 102
Building Alarm 5 Return NOTE “Return“ indicates connection to electronics circuit ground. “Common” indicates connection to common side of isolated relay contact. 4-42 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 103
NOTE Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. NOTE Alarm relay wiring should be a minimum of 22 AWG Figure 4‐36. Typical Alarm Relay Connection 4-43 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 104
NOTE A jumper wire must be connected between pins 1 and 2 on TB1, if the normally-closed REPO contact is not used. Figure 4‐37. Terminal Blocks TB1, TB2, and TB3 Connector Assignments 4-44 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
11. Reinstall the front door removed in Step 3 and secure with the retained hardware. 12. If wiring X-Slot connections, proceed to paragraph 4.9.3; otherwise, proceed to Step 13. 13. Close the door and secure the latch. 4-45 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 106
48 Vdc Battery Shunt Trip − NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG. Figure 4‐39. Typical Battery Interface Connection – Separate Battery System 4-46 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
NOTE When installing external wiring to X-Slot cards, conduit must be installed to the UPS cabinet. When installing internal wiring to X-Slot terminals, route the wiring through the internal opening in the X-Slot communication bay. For installation and setup of an X-Slot card, contact an Eaton service representative (see page 1-11). To install wiring to connections: If not already installed, install the LAN and telephone drops.
NOTE The REPO switch must be a normally-open or normally-closed latching‐type switch not tied into any other circuits. NOTE This procedure is intended for installing the Eaton-supplied REPO switch. If installing another manufacturer's switch, use this procedure only as a guide.
Page 109
REPO switch must be a latching-type switch not tied to any other circuits. NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common. Figure 4‐42. Normally-Open REPO Switch Wiring 4-49 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 110
REPO switch must be a latching-type switch not tied to any other circuits. NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common. Figure 4‐43. Normally‐Closed REPO Switch Wiring 4-50 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Service Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
- A ground conductor is properly installed. - Air conditioning equipment is installed and operating correctly. - The area around the installed UPS system is clean and dust‐free. (Eaton recommends that the UPS be installed on a level floor suitable for computer or electronic equipment.) - Adequate workspace exists around the UPS and other cabinets.
Page 113
- Pull-chain wiring between the UPS cabinets is properly installed. - Adequate workspace exists around the UPS cabinets, the tie cabinet, and other cabinets. - Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. 4-53 164201725 Rev 4 www.eaton.com/powerquality...
Install the Powerware Hot Sync CAN Bridge Card into an open X-Slot communication bay on the front of the UPS. See Figure 4‐34 on page 4-41 and Figure 4‐40 on page 4-47 for X-Slot communication bay locations. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 116
RIM II (see paragraph 5.4) SCM II (see paragraph 5.5) To locate the appropriate terminals on the Powerware Hot Sync CAN Bridge Card, see Figure 5‐2 and Table 5‐1. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 117
Alarm Relay NO Normally‐open contact closes when UPS is on bypass. RMP II, RIM II, and SCM II connections. CAN L Can H CAN input for parallel operation. Shield 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
NOTE Setup of the Powerware Hot Sync CAN Bridge Card for parallel operation must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 12. Reinstall the top internal safety shield panel and secure with the retained hardware.
Page 121
NOTE Use twisted-pair wiring between the UPS and MOB AUX contacts. NOTE Always confirm contact operation prior to wiring. Figure 5‐6. Distributed Bypass Pull-Chain Wiring with MOBs 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 122
MOB 2 Aux 2 Com MOB 2 Aux 2 Com MOB 3 Aux 2 Com Pull Chain MOB Common MOB 3 Aux 2 Com MOB 4 Aux 2 Com 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Figure 5‐8, and Table 5‐5 for the terminal location and wiring information. Close the front door and secure the latch. 10. Restart the UPS. See Chapter 7, “UPS Operating Instructions,” for startup instructions. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
INSTALLING OPTIONS AND ACCESSORIES NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 11. To check the operation of the RMP II, ensure that the UPS is supplying the load via inverter or bypass.
Page 126
10. Restart the UPS. See Chapter 7, “UPS Operating Instructions,” for startup instructions. NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date.
120 Vac Power Ground Terminal Terminal TB2 Customer Supervisory Contact Interface Terminal TB1 Signal Connections from the UPS Figure 5‐10. Supervisory Contact Module II Terminal Location 5-13 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 128
INSTALLING OPTIONS AND ACCESSORIES NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. Install wiring between the SCM II terminal block TB2 and the monitoring equipment.
Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5‐12. Remote Monitor Panel II Dimensions 5-15 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 130
Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5‐13. Relay Interface Module II Dimensions 5-16 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 131
Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5‐14. Supervisory Contact Module II Dimensions 5-17 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 132
INSTALLING OPTIONS AND ACCESSORIES This page intentionally left blank. 5-18 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 133
Section II Operation 5-19 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Understanding UPS Operation Figure UPS System Overview The Eaton 9395 UPS is a continuous-duty, solid‐state, transformerless (at 480 Vac), three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load. The basic system consists of a rectifier, battery converter, inverter, monitoring/operation control panel, integrated communication server, and digital signal processor (DSP) logic.
6.2.1 Modes The Eaton 9395 UPS supports a critical load in five different modes of operation: NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive. In Online mode, the critical load is supplied by the inverter, which derives its power from rectified utility AC power.
NOTE On a UPS configured with a Continuous Static Switch (CSS), bypass breaker (CB4) is not present. Figure 6‐2. Path of Current Through the UPS in Online Mode 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
UPM is highest when loads are greater than 50% of the system rating. Therefore, with multiple UPMs, a UPS can achieve higher efficiencies for lighter loads. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
The backfeed protection contactor is normally closed, ready to support the static switch unless the bypass input source becomes unavailable. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
K5 also opens. The opening of contactors K1 and K5 prevent system voltages from bleeding backwards through the static switch and rectifier snubber components to the utility source. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Rectifier Feed, Separate Battery, IOM Configuration 9395-825/825 9395-825/650 Single Reverse Transfer UPS – Four UPM, Common Figure 6‐19 on page 6-24 9395-825/750 Rectifier Feed, Common Battery, IOM Configuration 9395-825/825 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 143
Figure 6‐28 on page 6-33 9395-825/750 Rectifier Feed, Separate Battery, IOM Configuration 9395-825/825 9395-825/650 Simplified Dual-Feed UPS with Maintenance Bypass Figure 6‐29 on page 6-34 9395-825/750 Panel 9395-825/825 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
DO NOT install both a source neutral and a bonding jumper. Figure 6‐5. UPS System – Three UPM, Common Rectifier Feed, Common Battery, Dual‐Feed Configuration, Momentary Static Switch 6-10 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
DO NOT install both a source neutral and a bonding jumper. Figure 6‐6. UPS System – Three UPM, Common Rectifier Feed, Separate Battery, Dual‐Feed Configuration, Momentary Static Switch 6-11 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
DO NOT install both a source neutral and a bonding jumper. Figure 6‐7. Plus 1 UPS System – Four UPM, Common Rectifier Feed, Common Battery, Dual‐Feed Configuration, Momentary Static Switch 6-12 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
DO NOT install both a source neutral and a bonding jumper. Figure 6‐8. Plus 1 UPS System – Four UPM, Common Rectifier Feed, Separate Battery, Dual‐Feed Configuration, Momentary Static Switch 6-13 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 148
DO NOT install both a source neutral and a bonding jumper. Figure 6‐9. UPS System – Three UPM, Common Rectifier Feed, Common Battery, Dual‐Feed Configuration, Continuous Static Switch 6-14 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 149
DO NOT install both a source neutral and a bonding jumper. Figure 6‐10. UPS System – Three UPM, Common Rectifier Feed, Separate Battery, Dual‐Feed Configuration, Continuous Static Switch 6-15 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
DO NOT install both a source neutral and a bonding jumper. Figure 6‐11. Plus 1 UPS System – Four UPM, Common Rectifier Feed, Common Battery, Dual‐Feed Configuration, Continuous Static Switch 6-16 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
DO NOT install both a source neutral and a bonding jumper. Figure 6‐12. Plus 1 UPS System – Four UPM, Common Rectifier Feed, Separate Battery, Dual‐Feed Configuration, Continuous Static Switch 6-17 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 152
DO NOT install both a source neutral and a bonding jumper. Figure 6‐13. 825/550 UPS System – Two UPM, Common Rectifier Feed, Common Battery, Dual‐Feed Configuration, Continuous Static Switch 6-18 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 153
DO NOT install both a source neutral and a bonding jumper. Figure 6‐14. 825/550 UPS System – Two UPM, Common Rectifier Feed, Separate Battery, Dual‐Feed Configuration, Continuous Static Switch 6-19 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 154
DO NOT install both a source neutral and a bonding jumper. Figure 6‐15. 825/550 UPS System – Three UPM, Common Rectifier Feed, Common Battery, Dual‐Feed Configuration, Continuous Static Switch 6-20 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 155
DO NOT install both a source neutral and a bonding jumper. Figure 6‐16. 825/550 UPS System – Three UPM, Common Rectifier Feed, Separate Battery, Dual‐Feed Configuration, Continuous Static Switch 6-21 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 156
DO NOT install both a source neutral and a bonding jumper. Figure 6‐17. UPS System – Three UPM, Common Rectifier Feed, Common Battery, IOM Configuration 6-22 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 157
DO NOT install both a source neutral and a bonding jumper. Figure 6‐18. UPS System – Three UPM, Common Rectifier Feed, Separate Battery, IOM Configuration 6-23 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 158
DO NOT install both a source neutral and a bonding jumper. Figure 6‐19. Plus 1 UPS System – Four UPM, Common Rectifier Feed, Common Battery, IOM Configuration 6-24 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 159
DO NOT install both a source neutral and a bonding jumper. Figure 6‐20. Plus 1 UPS System – Four UPM, Common Rectifier Feed, Separate Battery, IOM Configuration 6-25 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
DO NOT install both a source neutral and a bonding jumper. Figure 6‐21. UPS System – Three UPM, Separate Rectifier Feed, Separate Battery, Dual‐Feed Configuration, Momentary Static Switch 6-26 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
DO NOT install both a source neutral and a bonding jumper. Figure 6‐22. Plus 1 UPS System – Four UPM, Separate Rectifier Feed, Separate Battery, Dual‐Feed Configuration, Momentary Static Switch 6-27 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 162
DO NOT install both a source neutral and a bonding jumper. Figure 6‐23. UPS System – Three UPM, Separate Rectifier Feed, Separate Battery, Dual‐Feed Configuration, Continuous Static Switch 6-28 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
DO NOT install both a source neutral and a bonding jumper. Figure 6‐24. Plus 1 UPS System – Four UPM, Separate Rectifier Feed, Separate Battery, Dual‐Feed Configuration, Continuous Static Switch 6-29 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 164
DO NOT install both a source neutral and a bonding jumper. Figure 6‐25. 825/550 UPS System – Two UPM, Separate Rectifier Feed, Separate Battery, Dual‐Feed Configuration, Continuous Static Switch 6-30 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 165
DO NOT install both a source neutral and a bonding jumper. Figure 6‐26. 825/550 UPS System – Three UPM, Separate Rectifier Feed, Separate Battery, Dual‐Feed Configuration, Continuous Static Switch 6-31 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 166
DO NOT install both a source neutral and a bonding jumper. Figure 6‐27. UPS System – Three UPM, Separate Rectifier Feed, Separate Battery, IOM Configuration 6-32 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 167
DO NOT install both a source neutral and a bonding jumper. Figure 6‐28. Plus 1 UPS System – Four UPM, Separate Rectifier Feed, Separate Battery, IOM Configuration 6-33 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 168
(BIB) is installed in the maintenance bypass and a single-feed UPS is being installed, a single feed to the maintenance bypass is acceptable for supplying both the UPS and the bypass. Figure 6‐29. Simplified Dual-Feed UPS with Maintenance Bypass Panel 6-34 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
6.4.1 Multiple UPS Parallel System Modes Similar to the single UPS system, the Eaton 9395 UPS parallel system supports a critical load in five different modes of operation. The standard operation modes are: NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
Page 170
Bypass mode. The distributed bypass system automatically returns to Online mode when the overload condition is cleared and system operation is restored within specified limits. 6-36 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
If more modules than can support the load must be taken offline, the load must be transferred to maintenance bypass or shut down. 6-37 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 172
In the Parallel Capacity (N+0) arrangement, if one UPS trips offline and goes to bypass, the remaining UPSs also go to bypass. 6-38 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
UPS 4 Battery Breakers Closed Output to Main Power Flow Critical Load Open Figure 6‐32. Path of Current through the UPSs in Battery Mode – Distributed Bypass 6-39 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 175
DO NOT install both a source neutral and a bonding jumper. Figure 6‐33. Typical Distributed Bypass System – Momentary Static Switch, 1+1 and 2+0 Configurations 6-41 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 176
DO NOT install both a source neutral and a bonding jumper. Figure 6‐34. Typical Distributed Bypass System – Momentary Static Switch, 2+1 and 3+0 Configurations 6-42 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 177
DO NOT install both a source neutral and a bonding jumper. Figure 6‐35. Typical Distributed Bypass System – Momentary Static Switch, 3+1 and 4+0 Configurations 6-43 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 178
DO NOT install both a source neutral and a bonding jumper. Figure 6‐36. Typical Distributed Bypass System – Continuous Static Switch, 1+1 and 2+0 Configurations 6-44 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 179
DO NOT install both a source neutral and a bonding jumper. Figure 6‐37. Typical Distributed Bypass System – Continuous Static Switch, 2+1 and 3+0 Configurations 6-45 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 180
DO NOT install both a source neutral and a bonding jumper. Figure 6‐38. Typical Distributed Bypass System – Continuous Static Switch, 3+1 and 4+0 Configurations 6-46 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
UPS operation. Figure 7‐1 or Figure 7‐2 shows the controls and indicators. Control Panel AC Input Breaker CB1 (Optional) (Not available with separate rectifier feed option) ISBM Figure 7‐1. UPS Controls and Indicators – Momentary Static Switch 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Circuit Breakers Optional circuit breaker (CB1) is used to control the AC input to the UPS rectifier. CB1 is not available with the separate UPM rectifier feed configuration. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
The following paragraphs describe using the UPS control panel to monitor the UPS. See paragraph 7.3 for use of the operational controls. When the unit powers up, the screen displays the Eaton logo as shown in Figure 7‐3. To advance to the Main Menu and Mimic screen, press any control panel pushbutton once.
LCD in the UPS status area. This message is also written to the Active Events Log and may be added to the History Log. The messages are divided into four categories: alarms, notices, status, and commands. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
LOAD OFF Figure 7‐4. Parts of the LCD The UPS status area automatically scrolls between the Eaton model number, current date and time, active alarms, active notices, and load percent and battery runtime for the UPS. If the Environmental Monitoring Probe is installed, the temperature and humidity sensed by the probe will also be displayed.
The Battery screen displays the battery voltage (Vdc), the battery current (Idc), the minutes of Battery – UPM battery time remaining, and battery temperature. Battery temperature must be set up by an authorized Eaton Customer Service Engineer. When battery life decreases to less than 20%, Check Battery is displayed. Statistics The Statistics screen displays the hours on line and the total kW hours used.
Page 188
VMMS UPM Redundancy screen. Use the up or down arrow pushbutton to set the number of UPMs. Press SAVE or ABORT. Once the action is completed, the Module Management System Setup screen is displayed. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 189
COM port to be set up, then press the SELECT pushbutton To return to the System Setup screen, press the ESC pushbutton 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
7.3.24 on page 7-27 or paragraph 7.4.27 on page 7-49. HOLD LOAD OFF BUTTON FOR 3 SECONDS TO TURN OFF LOAD CANCEL LOAD OFF Figure 7‐6. Load Off Screen 7-10 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 192
Charger Off Turns the battery charger off. NOTE The Energy Saver System and Variable Module Management System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer NOTE Variable Module Management System and Energy Saver System modes are mutually exclusive.
UPS transfers to Online mode. The status indicator on the UPS control panel indicates the UPS is in Bypass mode. If Auto Bypass is not enabled, the UPS output remains off until the UPS transfers to Online mode. 7-13 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
The Online status indicator is illuminated. The UPS status indicates ONLINE + ESS. The UPM status indicates ONLINE. If the battery is not charging, the power module is off. 7-14 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
The UPS transfers to Battery mode and then to Online mode in approximately ten seconds. The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicates ONLINE. 7-16 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
UPS Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
The Online status indicator is illuminated. The UPS status indicates ONLINE + ESS. The UPM status indicates ONLINE. If the battery is not charging, the power module is off. 7-18 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
System Status menu bar. The Bypass CONTROLS Control Command screen is displayed. On the Bypass Control Command screen, select DISABLE VAR MODULE MANAGEMENT 7-20 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Bypass Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
Page 202
UPS is ready to transfer to the Online mode and supply the critical load. 21. If the UPS is a Plus 1 model or an upgraded 825/550, repeat Steps 12 through 15 selecting to start UPM 4. UPM 4 7-22 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
16. Verify the following messages display sequentially on the UPM status line: DC STARTING, CHARGER OFF INVERTER STARTING INVERTER SYNCING READY The UPM rectifier and inverter turn on. 7-23 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
UPS Command menu bar. SELECT The UPS transfers to Online mode. If the power module is not available, the system remains on bypass and an alarm sounds. 7-24 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
The System Status CONTROLS screen is displayed. On the System Status screen, select the command. The UPS Control Command screen is displayed. 7-25 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
UPM GO TO ONLINE 10. Press the pushbutton on the UPM Command menu bar. SELECT The UPM transfers to Online mode. The UPM status indicates ONLINE. 7-26 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Bypass Control Command screen. The UPS controls the UPS output by LOAD OFF powering down the UPS and de‐energizing the critical load. The UPS (including Bypass) remains off until restarted. 7-27 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 208
When LOAD OFF is selected and held for three seconds, the input, output, battery, and bypass backfeed contactors open, and the power module is turned off. 7-28 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
Page 210
UPS OPERATING INSTRUCTIONS Activated Deactivated Pushbutton locked into place Unlock pushbutton to release Figure 7‐8. REPO Operation 7-30 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
UPS is in Bypass mode. If Auto Bypass is not enabled, the UPS outputs remain off until the UPSs transfer to Online mode. 7-31 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
The Online status indicator is illuminated. The UPS status indicates ONLINE + ESS. The UPM status indicates ONLINE. If the battery is not charging, the power module is off. 7-32 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
The UPS transfers to Battery mode and then to Online mode in approximately ten seconds. The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicates ONLINE. 7-34 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
UPS Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
The Online status indicator is illuminated. The UPS status indicates ONLINE + ESS. The UPM status indicates ONLINE. If the battery is not charging, the power module is off. 7-36 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
System Status menu bar. The Bypass CONTROLS Control Command screen is displayed. On the Bypass Control Command screen, select DISABLE VAR MODULE MANAGEMENT 7-38 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Bypass Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
Page 220
20. Verify the following messages display sequentially on the UPM status line: DC STARTING, CHARGER OFF INVERTER STARTING INVERTER SYNCING READY The UPM 3 rectifier and inverter turn on. 7-40 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
UPM Control Command screen is displayed. 14. On the UPM Control Command screen, select UPM ON 15. Press the pushbutton on the UPM Command menu bar. SELECT 7-41 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
If not already closed, close the battery breaker. On any UPS, press the pushbutton on the main menu bar. The System CONTROLS Status screen is displayed. 7-42 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
13. If the UPS is a Plus 1 model or an upgraded 825/550, repeat Steps 4 through 10 selecting to shut down UPM 4. UPM 4 14. Repeat Steps 2 through 13 for each UPS in the distributed bypass system. 7-43 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
CONTROLS UPM Control Command screen is displayed. On the UPM Control Command screen, select UPM ON Press the pushbutton on the UPM Command menu bar. SELECT 7-44 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
UPS being shut down. Logic power remains on. Verify the battery breaker or disconnect for the UPS being shut down is open. If not, open the breaker. 7-45 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
The remaining UPMs supply the critical load. Logic power remains on. 12. Repeat Steps 8 through 11 selecting to shut down UPM 2. UPM 2 7-46 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
11. Verify External Communications Failure alarm has cleared and no other alarms are active on the online UPSs. 12. On the System Status screen, select the command. 7-47 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
On the System Status screen, select the command. CHARGER Press the pushbutton on the System Status menu bar. The Charger CONTROLS Control Command screen is displayed. 7-48 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and cleared. Restart the UPS after pressing the pushbutton by following the LOAD OFF procedure in paragraph 7.4.1 on page 7-31 or 7.4.8 on page 7-35. 7-49 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 230
7.4.1 on page 7-31 or 7.4.8 on page 7-35. W A R N I N G Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. 7-50 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
Page 232
UPS OPERATING INSTRUCTIONS This page intentionally left blank. 7-52 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Chapter 8 Communication Figure This chapter describes the communication features of the Eaton 9395 UPS and provides information about connecting hardware and using Terminal mode. For terminal wiring information, see paragraph 3.2.3 on page 3-27 and paragraph 4.9 on page 4-40. For location of the customer interface panels and terminals, see Figure 4‐23 on page 4-27 and Figure 4‐34 through Figure 4‐37 starting on page 4-41.
Eaton 9395 UPS: Proactive monitoring, called Anomaly Detection, automatically analyzes the status of the Eaton 9395 UPS on a daily basis. All data gathered from the unit, current and historical, is analyzed at the Customer Reliability Center (CRC) for trending issues.
The eNotify Service relies on a ConnectUPS-X Web/SNMP Card (or Power Xpert Gateway Card ) installed with the UPS sending one-way status and event e-mails to Eaton Remote Monitoring servers that analyze and store the data. Those servers also take the appropriate actions of sending notifications and reports. The ConnectUPS Card gathers information from the UPS directly and from any external sensors that are attached.
See paragraph 7.2 on page 7-3, “Using the Control Panel,” for instructions on navigating the control panel. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
If a port is operating in Terminal mode and is connected to a computer, you can press [Esc] [H] to print the entire log with a firmware version header. The log in Terminal mode is always in English. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 238
102 NOTICE: INVERTER L1 CURRENT LIMIT (PM1) 103 NOTICE: INVERTER L2 CURRENT LIMIT (PM1) 104 NOTICE: INVERTER L3 CURRENT LIMIT (PM1) Figure 8‐2. Sample Event History Log 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
The RMP II can be flush‐mounted or surface‐mounted on a desktop, or secured to a wall. Figure 8‐3 shows an RMP II front panel. Figure 8‐3. Remote Monitor Panel II Front Panel 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 240
The UPS is preparing to shut down because the UPS is in Battery mode and the DC voltage is approaching its low limit. This indicator is accompanied by a horn. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Contacts are closed when approximately two minutes of battery time is remaining before the critical load is lost. UTILITY FAILURE Pins 6 and 15 Contacts are closed when Utility Failure is detected. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
BYPASS NOT AVAILABLE TB2‐10 through TB2‐12 ON BATTERY TB2‐13 through TB2‐15 UPS ALARM TB2‐16 through TB2‐18 ON BYPASS TB2‐19 through TB2‐21 SHUTDOWN IMMINENT TB2‐22 through TB2‐24 8-10 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Eaton service representative. If the string requires service, refer to the battery manufacturer's operating manual for instructions on battery maintenance or contact an Eaton service representative. Observe these precautions when working on or around batteries: Remove watches, rings, or other metal objects.
Check the UPS air filters (located behind the front panels or door) and wash or replace as necessary. See Figure 9‐1 or Figure 9‐2 and Figure 9‐3 or Figure 9‐4 for filter locations, and Table 9‐1 for filter sizes. Contact an Eaton service representative for replacement filters. To remove the filters: Table 9‐1.
Page 245
If opened, close the front door and secure the latch. Bottom Left ISBM Air Filters Figure 9‐1. ISBM Section Air Filter Locations – Momentary Static Switch 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 246
UPS MAINTENANCE Middle Right ISBM Air Filter Bottom Left ISBM Air Filters Bottom Right ISBM Air Filters Figure 9‐2. ISBM Section Air Filter Locations – Continuous Static Switch 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 247
UPS MAINTENANCE UPM Air Filters Figure 9‐3. Two UPM Section Air Filter Locations 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 248
(FI-UPM) air filter (located behind the front panel) and wash or replace as necessary. See Figure 9‐5 for the filter location. The FI-UPM filter size is 20” 44” 0.25”. Contact an Eaton service representative for a replacement filter. To remove the filter: a.
Eaton service representative for more information about service offerings. 9.2.5 BATTERY Maintenance Contact an Eaton service representative for battery maintenance. Battery replacement and maintenance should be performed only by authorized service personnel. 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Maintenance Training A basic training course, available from Eaton Corporation, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Help Desk (see page 1-11).
Configurable per UPM at nominal line voltage: Up to 120A with less than 85% load Up to 80A with 100% load Battery Shunt Trip 48 Vdc 10-1 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Electrostatic Discharge (ESD) Meets IEC 801‐2 specifications. Withstands up to 25 kV pulse Immunity without damage and with no disturbance or adverse effect to the critical load. 10-2 164201725 Rev 4 www.eaton.com/powerquality Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual...
Page 253
-built battery cabinets (individually and collectively, the ”Warranted Items”) are free from defects in material and workmanship. If, in the opinion of Eaton, a Warranted Item is defective and the defect is within the terms of this Warranty, Eaton's sole obligation will be to repair or replace such defective item (including by providing service, parts, and labor, as applicable), at the option of Eaton.