Output - Endress+Hauser Proline Prosonic Flow 93 Operating Instructions Manual

Foundation fieldbus ultrasonic flow measuring system
Hide thumbs Also See for Proline Prosonic Flow 93:
Table of Contents

Advertisement

Technical data
Output signal
Signal on alarm
Link Master (LM)
support
Link Master
Basic Device
Device basic current
Device starting current
Device error current (FDE)
Device (lift off)
min. voltage
Permissible fieldbus supply
voltage
Integrated reverse polarity
protection
ITK Version
Number of VCRs (total)
Number of link objects in VFD
Device capacitance
Galvanic isolation
Data transmission speed
Signal coding
116
10.1.4

Output

Physical data transmission (Physical Layer Type):
• Fieldbus interface in accordance with IEC 61158-2
• Corresponds to device version type 512 of the FOUNDATION Fieldbus specification:
type 512 – standard data transfer (±9 mA, symmetrical), separate supply to field device (4-wire),
intrinsically safe version of the FF interface, FISCO
• With integrated reverse polarity protection
Status messages as per FOUNDATION Fieldbus specification
Yes
Factory setting
Selectable
11 mA
<11 mA
0 mA
9 V (H1-segment)
9 to 32 V
Yes
5.01
48
40
In accordance with IEC 60079-27, FISCO/FNICO
All circuits for inputs, outputs and power supply are galvanically isolated from each other.
31.25 kbit/s, voltage mode
Manchester II
Proline Prosonic Flow 93 FOUNDATION Fieldbus