Proline Prosonic Flow 93 FOUNDATION Fieldbus
No.
Error messages:
FOUNDATION Fieldbus
(FF)*
(local display)
No. # 6xx Simulation mode active
602
Device status message (FF):
Positive zero return active CH1
– Err. No. 602
Local display:
S: POS. 0-RET. CH1
!: # 602
603
Device status message (FF):
Positive zero return active CH2
– Err. No. 603
Local display:
S: POS. 0-RET. CH2
!: # 603
604
Device status message (FF):
Positive zero return active
CH1&2 – Err. No. 604
Local display:
S: POS. 0-RET. CH1&2
!: # 604
691
Device status message (FF):
Simulation failsafe active –
Err. No. 691
Local display:
S: SIM. FAILSAFE.
!: # 691
692
Device status message (FF):
Simulation Volume flow active
- Err. No. 692
Local display:
S: SIM. MEASURAND
!: # 692
Endress+Hauser
Transducer Block
error messages
"Diagnosis" Transducer
Block
BLOCK_ERR = No Error
OUT. SUBSTATUS = Non specific
BLOCK_ERR = No Error
OUT. SUBSTATUS = Non
specific1
BLOCK_ERR = No Error
OUT. SUBSTATUS = Non specific
BLOCK_ERR = Simulation
OUT. QUALITY = UNCERTAIN
active
Transducer_Error = No Error
OUT. SUBSTATUS = Non specific
BLOCK_ERR = Simulation
OUT. QUALITY = UNCERTAIN
active
Transducer_Error = No Error
Analog Input Function Block
error messages
OUT. QUALITY = UNCERTAIN
OUT. QUALITY = UNCERTAIN
OUT. QUALITY = UNCERTAIN
OUT. SUBSTATUS = Non specific
Troubleshooting
Reason for error/rectification
(spare parts ä 109)
Cause:
Positive zero return is active.
Remedy:
Deactivate positive zero return:
• FF: Transducer Block "Transducer_CH1" (base
index: 1400) or Transducer Block
"Transducer_CH2" (base index: 1500)
Parameter "Sys. - Positive Zero Return" OFF
• Local display: BASIC FUNCTIONS SYSTEM
PARAMETERS CONFIGURATION POS.
ZERO RETURN ( OFF)
Cause:
Simulation of response to error (outputs) is active
Remedy:
Switch off simulation:
• FF: "Diagnosis" Transducer Block (base index:
1600) "Sys. – Sim.Failsafe Mode" parameter
OFF
• Local display: SUPERVISION
SYSTEM OPERATION SIM. FAILSAFE
MODE ( OFF)
Cause:
Simulation of measured variable is active.
Remedy:
Switch off simulation:
• FF: "Flow" Transducer Block (base index: 1400)
"Simulation - Measurand" parameter OFF
• Local display: SUPERVISION SYSTEM
OPERATION SIM. MEASURAND ( OFF)
105