Wiring
60
4.1.6

Bus termination

The start and end of each fieldbus segment are always to be terminated with a bus terminator. With
various junction boxes (non-Ex), the bus termination can be activated via a switch. If this is not the
case, a separate bus terminator must be installed. Note the following points:
• In the case of a branched bus segment, the device furthest from the segment coupler represents
the end of the bus.
• If the fieldbus is extended with a repeater then the extension must also be terminated at both
ends.
4.1.7

Further information

General information and further notes on connections can be found on the website
(www.fieldbus.org) of the Fieldbus Foundation or in the Operating Instructions "FOUNDATION
Fieldbus Overview" (acquired at: www.endress.com  Download).