Proline Prosonic Flow 93 FOUNDATION Fieldbus
!
Endress+Hauser
Display text (xxx... = serial number)
ARITHMETIC_xxxxxxxxxxx
INPUT_SELECTOR_xxxxxxxxxxx
SIGNAL_CHARACT_xxxxxxxxxxx
INTEGRATOR_xxxxxxxxxxx
Note!
This measuring device is supplied with the bus address "250" and is thus in the address range
reserved for readdressing field devices, between 248 and 251. This means that the LAS (Link Active
Scheduler) automatically assigns the device a free bus address in the initialization phase.
5.
Identify the field device using the DEVICE_ID that you noted down and assign the desired field
device tag name (PD_TAG) to the fieldbus device in question.
Factory setting: EH_PROSONIC_FLOW_93_xxxxxxxxxxx
Configuration of the "Resource Block" (base index 400)
6.
Open the Resource Block.
7.
On delivery, hardware write protection is disabled so that you can access all the write
parameters via FOUNDATION Fieldbus. Check this status via the parameter WRITE_LOCK:
– Write protection activated = LOCKED
– Write protection deactivated = NOT LOCKED
Deactivate the write protection if necessary  ä 78.
8.
Enter the desired block name (optional).
Factory setting: RESOURCE_ xxxxxxxxxxx
9.
Set the operating mode in the parameter group MODE_BLK (parameter TARGET) to AUTO.
Configuration of the "Transducer Blocks"
The individual Transducer Blocks comprise various parameter groups ordered by device-specific
functions:
Transducer Block
Transducer Block "Flow Channel 1"
Transducer Block "Flow Channel 2"
"Diagnosis" Transducer Block
Transducer Block "Service"
"Display" Transducer Block
"Totalizer" Transducer Block
The following description provides an example for the "Flow Channel 1" Transducer Block
(base index: 1400).
10. Enter the desired block name (optional).
Factory setting: TRANSDUCER_CH1_xxxxxxxxxxx
11. Open the "Flow Channel 1" Transducer Block.
Base index
Description
1100
Arithmetic Function Block (ARTH)
1150
Input Selector Function Block (ISEL)
1200
Signal Characterizer Function Block (CHAR)
1250
Integrator Function Block (INTG)
Base index
Description
1400
Flow measurement channel 1
1500
Flow measurement channel 2
1600
Diagnostic functions
1700
Service functions
1800
Local display functions
1900
Totalizer 1 to 3
Commissioning
81