Installation
12
3.2.3

Orientation

Vertical orientation
We recommend the sensor be mounted where there is upward direction of flow. With this
orientation, entrained solids will sink down and gases will rise away from the sensor when the fluid
is stagnant.
Horizontal orientation
We recommend the sensors be mounted within an angle of ±60° to the horizontal (area shaded gray
in the graphic). With this orientation, flow measurement is less affected by any gas or air
accumulation in the upper area of the pipe or by buildup at the bottom of the pipe.
A
Fig. 5:
Recommended orientation and recommended installation range
A
Recommended orientation with upward direction of flow
B
Recommended installation range with horizontal orientation
C
Recommended installation range max. 120°
3.2.4

Inlet and outlet run

If possible, install the sensor well clear of assemblies such as valves, T-pieces, elbows, etc.
Compliance with the following inlet and outlet runs is required in order to ensure measuring
accuracy.
³ 15 x DN
³ 20 x DN
1
³ 20 x DN
2
³ 15 x DN
3
Fig. 6:
Recommended inlet and outlet runs to comply with measuring accuracy specifications
A
Clamp-on version
B
Insertion version
1
= values for single-path version
2
= values for two-path version
1
Valve (2/3 open)
2
Pump
3
Two pipe bends in different directions
Proline Prosonic Flow 93 FOUNDATION Fieldbus
C
³ 3 x DN
A
1
2
3
C
B
1
1
³ 15 x DN
³ 3 x DN
³ 3 x DN
³ 10 x DN
2
2
B
³ 20 x DN
1
³ 20 x DN
2
³ 20 x DN
1
³ 15 x DN
2
³ 15 x DN
1
³ 10 x DN
2
Endress+Hauser
A0001105