Output

Current output
4 to 20 mA with superimposed digital communication protocol HART, 2-wire
The current output offers a choice of three different operating modes:
• 4.0 to 20.5 mA
• NAMUR NE 43: 3.8 to 20.5 mA (factory setting)
• US mode: 3.9 to 20.8 mA
Signal on alarm in accordance with NAMUR recommendation NE 43.
4 to 20 mA HART:
Options:
• Max alarm: can be set from 21.5 to 23 mA
• Min. alarm: < 3.6 mA (factory setting)
4 to 20 mA HART
R
L max
[ ] W
1065
848
10.5
1
Power supply 10.5 to 30 VDC Ex i
2
Power supply 10.5 to 35 VDC, for other types of protection and non-certified device versions
3
R
maximum load resistance
Lmax
U
Supply voltage
Operation via handheld terminal or PC with operating program: take minimum communication
resistance of 250 Ω into consideration.
A damping affects all outputs (output signal, display). Damping can be enabled as follows:
• Via the onsite display, Bluetooth, handheld terminal or PC with operating program, continuous
from 0 to 999 seconds
• Factory setting: 1 s
See the separate technical documentation (Safety Instructions (XA)) on
www.endress.com/download.
The device' s linearization function allows the user to convert the measured value to any units of
height or volume. User-defined linearization tables of up to 32 value pairs can be entered if
necessary.
HART
• Manufacturer ID: 17 (0x11{hex})
• Device type ID: 0x112A
• Device revision: 1
• HART specification: 7