Endress+Hauser Proline Prosonic Flow 93 Operating Instructions Manual page 99

Foundation fieldbus ultrasonic flow measuring system
Hide thumbs Also See for Proline Prosonic Flow 93:
Table of Contents

Advertisement

Proline Prosonic Flow 93 FOUNDATION Fieldbus
Endress+Hauser
Transducer Block
The device description file (Device Description, DD) has not been loaded into the host
system or the configuration program  Load the file into the configuration system.
The manufacturer-specific
parameters are not visible.
Reference sources of the DD  ä 109
!
Ensure you use the correct system files for linking the field devices into the host system.
Appropriate version information can be called up in the measuring device via the following
functions/parameters:
Local display:
• HOME  BASIC FUNCTIONS  FOUND. FIELDBUS  INFORMATION  DEVICE
REVISION (6243)
• HOME  BASIC FUNCTIONS  FOUND. FIELDBUS  INFORMATION  DD
REVISION (6244)
FF configuration program:
• Resource Block  Parameter DEV_REV
• Resource Block  Parameter DD_REV
Example (local display): Display in the DEVICE REVISION (6243) function  03
Display in the DD REVISION (6244) function  01
Required device description file (DD)  0301.sym / 0301.ffo
Simulation is active  Deactivate simulation via parameter group SIMULATE.
Analog Input fct. block: The
output value OUT is not
updated despite having a
GOOD status.
Æ
Error messages
Error messages in the FF configuration program  ä 101
Error messages on the local display  ä 101
Æ
Other error (without error message)
Diagnosis and rectification  ä 108
Some other error has
occurred.
Note!
Troubleshooting