Power Supply - Endress+Hauser Proline Prosonic Flow 93 Operating Instructions Manual

Foundation fieldbus ultrasonic flow measuring system
Hide thumbs Also See for Proline Prosonic Flow 93:
Table of Contents

Advertisement

Proline Prosonic Flow 93 FOUNDATION Fieldbus
Measuring unit electrical
connection
Connecting the connecting
cable
Supply voltage
Cable entry
Cable specifications
Endress+Hauser
10.1.5

Power supply

 ä 61
 ä 61
Transmitter
Current output / HART
• 85 to 260 V AC, 45 to 65 Hz
• 20 to 55 V AC, 45 to 65 Hz
• 16 to 62 V DC
Sensor
• Powered by the transmitter
Power supply and signal cables (inputs/outputs)
• Cable entry M20 × 1.5 (8 to 12 mm / 0.31 to 0.47")
• Cable gland for cables, 6 to 12 mm (0.24 to 0.47")
• Thread for cable entry ½" NPT, G ½"
Connecting cable (sensor/transmitter)
Prosonic Flow P/W
Sensor DN 15 to 65 (½ to 2½")
Cable gland for one multi core connecting cable (1 × Ø 8 mm /0.31 in) per cable entry
• Cable gland M20 × 1.5
• Thread for cable entry ½" NPT, G ½"
Prosonic Flow P/W
Sensor DN 50 to 4000 (2 to 160")
Cable gland for two single core connecting cables (2 × Ø 4 mm /0.16 in) per cable entry
• Cable gland M20 × 1.5
• Thread for cable entry ½" NPT, G ½"
Fig. 87:
Cable gland for two connecting cables (2 × Ø 4 mm / 0.16 in) per cable entry
Only use the connecting cables supplied by Endress+Hauser.
Different versions of the connecting cables are available  ä 92.
Prosonic Flow P
• Cable material:
– Prosonic Flow 93P (DN 50 to 4000 / 2 to 160"): PVC (standard) or
PTFE (for higher temperatures)
– Prosonic Flow 93P (DN 15 to 65 / ½ to 2½"): TPE-V
• Cable length:
– For use in a non-hazardous zone: 5 to 60 m (16.4 to 196.8 ft)
– For use in a hazardous zone: 5 to 30 m (16.4 to 98.4 ft)
Technical data
A0008152
119