2.2 Mechanical Installation

2.2
Mechanical Installation
This section outlines specifications, procedures, and the environment for proper mechanical installation of the drive and
harmonic filter module.
◆ Installation Environment
To help prolong the optimum performance life of the drive, install the drive in an environmental matching the
specifications in
Table 2.1
CIMR-U20028 to 20248, 40011 to 40930
Table 2.1 Installation Environment (CIMR-U20028 to 20248, 40011 to 40930)
Environment
Installation Area
Ambient Temperature
Humidity
Storage Temperature
Surrounding Area
Altitude
Vibration
Orientation
NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive as the noise created can lead to
erroneous operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the drive during installation. Failure to
comply could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the
temporary cover before startup, as the cover will reduce ventilation and cause the drive to overheat.
Harmonic Filter Module
Environment
Installation Area
Ambient Temperature
Humidity
Storage Temperature
Surrounding Area
Altitude
Vibration
Orientation
NOTICE: Avoid placing harmonic filter module peripheral devices, transformers, or other electronics near the harmonic filter module
as the noise created can lead to erroneous operation. If such devices must be used in close proximity to the harmonic filter module,
take proper steps to shield the harmonic filter module from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the harmonic filter module during
installation. Failure to comply could result in damage to the harmonic filter module. Place a temporary cover over the top of the
50
and
Table
2.2.
Indoors
-10 to 40°C (IP20/NEMA 1, UL Type 1 enclosure)
-10 to 50°C (IP00 enclosure)
Drive reliability improves in environments without wide temperature fluctuations.
When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature inside the enclosure
does not exceed the specified levels.
Do not allow ice to develop on the drive.
95% RH or less and free of condensation
-20°C to +60°C
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
1000 m, up to 3000 m with derating (for details, refer to
10 to 20 Hz: 9.8 m/s
2
(40477 to 40930: 5.9 m/s
20 to 55 Hz: 5.9 m/s
2
(20104 to 20248, 40096 to 40930: 2.0 m/s
Install the drive vertically to maintain maximum cooling effects.
Table 2.2 Installation Environment (Harmonic Filter Module)
Indoors
IP00 enclosure: -10°C to +50°C
Harmonic filter module reliability improves in environments without wide temperature fluctuations.
When using the harmonic filter module in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature
inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the harmonic filter module.
95% RH or less and free of condensation
-20°C to +60°C
Install the harmonic filter module in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
1000 m, up to 3000 m with derating (for details, refer to
10 to 20 Hz: 5.9 m/s
2
20 to 55 Hz: 2.0 m/s
2
Install the harmonic filter module vertically to maintain maximum cooling effects.
Conditions
Altitude Derating on page
463)
2
)
2
)
Conditions
Altitude Derating on page
463)