Setting 62: Memobus Regs1 (It selects it with H2-07 and H2-08.)
The contact output is closed if any of the bits that are specified by H2-08 for the MEMOBUS/Modbus register address
that is set in H2-07 turns on.
Setting 63: Memobus Regs2 (It selects it with H2-09 and H2-10.)
The contact output is closed if any of the bits that are specified by H2-10 for the MEMOBUS/Modbus register address
that is set in H2-09 turns on.
Setting 64: During commercial power operation
Output closes when operating on commercial power when commercial power switching is selected (b1-24 = 1).
Setting 90 to 92: DriveWorksEZ digital output 1 to 3
These settings are for output functions used in DriveWorksEZ. Normally there is no need to change these settings.
Setting 100 to 192: Functions 0 to 92 with inverse output
These settings have the same function as settings 0 to 92 but with inverse output. Set as 1, where the "1" indicates
inverse output and the last two digits specify the setting number of the function.
Examples: For inverse output of "8: During baseblock", set 108.
H2-06: Power Consumption Output Unit Selection
Sets the units for the output signal when one of the multi-function terminals is set to power consumption pulse output
(H2-01, H2-02, or H2-03 = 39) or regenerated power pulse output (H2-01, H2-02, or H2-03 = 3A).
This output function provides a watt hour meter or a PLC input by a 200 ms pulse signal. H2-06 determines the
frequency that pulses are issued to keep track of the kWh for the drive.
No.
H2-06
<1> The setting range is 1 to 4 in the drive software versions S1014 and earlier.
Note: 1. A regenerated power pulse output does not subtract from the total watt hours during powering. A power consumption output does not
subtract from the total watt hours during regeneration.
2. The drive keeps track of the watt hours as long as the control circuit has power. The value is reset when the power supply is shut off.
Figure 5.78
(Watt Hour Output Unit Selection)
Multi-function Output)
H2-07 to H2-10: Memobus Regs
These parameters specify the MEMOBUS/Modbus registers and bits from which data will be sent to the multi-function
contact outputs.
No.
H2-07
H2-08
H2-09
H2-10
The MEMOBUS/Modbus register addresses for sending data to multi-function digital outputs 62 and 63 are specified in
H2-07 and H2-09, and the bits for the MEMOBUS/Modbus registers are specified in H2-08 and H2-10.
YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
Parameter Name
Power Consumption Output Unit Selection
H2-06
Integral Power
H2-01 to H2-03
OFF
Figure 5.78 Watt Hour Output Example
Name
Memobus Regs1 Address Select
Memobus Regs1 Bit Select
Memobus Regs2 Address Select
Memobus Regs2 Bit Select
5.7 H: Terminal Functions
Setting Range
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
ON
OFF
0.2 s
Setting Range
1 to 1FFFH
0 to FFFFH
1 to 1FFFH
0 to FFFFH
Default
<1>
1
5
Default
1
0
1
0
285

Advertisement

Table of Contents
loading

Table of Contents