V Control Power Supply Unit Specifications - YASKAWA U1000 Series Technical Manual

Low harmonics regenerative matrix converter
Hide thumbs Also See for U1000 Series:
Table of Contents

Advertisement

3.14 24 V Control Power Supply Unit Wiring
Wire Gauges and Tightening Torques
Tightening
Terminal
Screw
Number
Size
24, 0, FE
M2
(1.95 to 2.21)
Ferrule-Type Wire Terminations
Crimp a ferrule to signal wiring to improve wiring simplicity and reliability. Use CRIMPFOX6, a crimping tool
manufactured by PHOENIX CONTACT.
Figure 3.81
Size mm
2
(AWG)
0.25 (24)
0.34 (22)
0.5 (20)
Power Supply and the Control Circuit
Table 3.31
outlines the various conditions under which the option provides power to the control circuit.
Drive Main Circuit Input Power Supply
ON
ON
OFF
OFF
UL and CE Compliance
External Power Supply
Use a Class 2 power supply as defined by UL standards for the customer-supplied power supply connection to the 24 V
Control Power Supply Unit.
◆ 24 V Control Power Supply Unit Specifications
Input Operating Voltage
Input Current
Consumption Power
Compliance
<1> Use a Class 2 power supply with a capacity of 24 V to comply with UL standards.
126
Table 3.29 Wire Gauges and Tightening Torques
Bare Cable
Torque
Recomm. Gauges
Nm
mm
2
(AWG)
(inlb)
0.22 to 0.25
0.75
(18 AWG)
Figure 3.80 Ferrule Dimensions
Table 3.30 Ferrule Terminal Types and Sizes
Type
AI 0.25-6YE
AI 0.25-6BU
AI 0.34-6TQ
AI 0.5-6WH
Table 3.31 Power Supply and Control Circuit
Power from 24 V Control Power Supply Unit
OFF
OFF
Table 3.32 24 V Control Power Supply Unit Specifications
Item
Applicable Gauges
Recomm. Gauges
mm
2
(AWG)
Standard wire:
0.25 to 1.0
(24 to 17 AWG)
Single line:
0.25 to 1.5
(24 to 16 AWG)
d1
d2
L (mm)
d1 (mm)
10.5
0.8
10.5
0.8
12
1.1
Control Circuit Operation in Drive
ON
ON
24 Vdc ± 20% (19.2 V to 28.8 V)
1.9 A
38 W
UL
, CE
<1>
YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
Crimp Terminals
Applicable Gauges
mm
2
(AWG)
mm
2
(AWG)
0.5
0.25 to 0.5
(20 AWG)
(24 to 20 AWG)
d2 (mm)
2.0
2.0
2.5
Operating
Stopping
Specifications
Wire Type
Shielded cable, etc.
Manufacturer
PHOENIX CONTACT
Drive Operation
Possible
Possible
Not possible
Not possible

Advertisement

Table of Contents
loading

Table of Contents